94
Problem
Reason
Help
Solution
AL6
The water heating coil
is starting to freeze.
NOTE! The ventilation
unit does not start until
the alarm state has
been removed and the
alarm has been reset by
pressing any button on
the control panel.
Insufficient isolation in the ducts.
Check the thickness of the insulation in the
supply air and the exhaust air ducts and
improve the insulation when required.
Contact a service representive.
The overheating protection of the
afterheater has been activated
Find out what has caused the error and reset
the over-heating protection (® button on
the coil)
Contact a service representive.
The ventilation unit's door is open
Close the door.
Contact a service representive.
Low room temperature
Nosta huonelämpötilaa.
Contact a service representive.
TE-30 error int the temperature sensor
Contact a service representive.
AL7
Supply air hot. Risk of
fire.
Error in the electrical after heater
Contact a service representive.
The water heater's valve actuator is
broken
Contact a service representive.
TE-10 error in the temperature sensor
Contact a service representive.
Fire risk
Contact a service representive.
AL8
Electrical re-heater or
pre-heater overheating
Error in the electrical after heater
Contact a service representive.
The supply air fan has stopped
Open the service hatch when
the unit is running. The exhaust
fan needs to be on. With the
LTR unit you must push down
the door coupling with a
screwdriver and check if the
unit starts.
Contact a service representive.
The supply air filter is clogged
Open the service hatch when
the unit is not on. Remove the
filters and check if they are
dirty.
Change the exhaust filter.
The outside air grille is clogged
Check if there is something
blocking the outside air grille.
Clean the outdoor air grille
Contact a service representive.
The heater controller card is broken
Replace the heater controller card
Contact a service representive.
Summary of Contents for eWind Pelican
Page 24: ...24 2016 1254 2014 ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PELICAN A 44 dB 374 m3 h...
Page 25: ...25 Ilmanvaihtolaitteen k ytt ja yll pito ohje...
Page 26: ...26 Pelican eWind Drift och underh llsanvisningar f r ventilationsaggregatet Svenska...
Page 48: ...48 2016 1254 2014 ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PELICAN A 44 dB 374 m3 h...
Page 49: ...49 Drift och underh llsanvisningar f r ventilationsaggregatet...
Page 50: ...50 Pelican eWind Drift och underh llsanvisningar f r ventilationsaggregatet Norsk...
Page 72: ...72 2016 1254 2014 ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PELICAN A 44 dB 374 m3 h...
Page 73: ...73 Drifts og vedlikeholdsinstrukser for ventilasjonsenheten...
Page 74: ...74 Pelican eWind Operating and maintenance instructions for the ventilation unit English...
Page 96: ...96 2016 1254 2014 ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PELICAN A 44 dB 374 m3 h...
Page 97: ...97 Operating and maintenance instructions for the ventilation unit...
Page 98: ......
Page 99: ......