Bentone B55/B65 RME
General
3. TECHNICAL DATA
3.1
Type designation B55-2/B65-2 RME
3.2
Dimensions
3.3
Recommended nozzle
and pressure
Because of the different boiler types, combustion
chamber geometries and combustion chamber loads
that exist, it is not possible to specify a given spray
angle or spray pattern.It should be noted that the spray
angle and spray pattern will vary depending on the
pump pressure.
290
595
B
610
321
400
405
C
D
Nozzle
45°S Danfoss
45°B Danfoss
60°S Danfoss
60°B Danfoss
Pump pressure
14 bar (12 - 16 bar)
On burners equipped with hydraulic air control or
optimization the oil pressure should not be less than 14
bar.
Length of
burner tube
B55
Flange
Measure B
Burner tube
Measure C
Burner tube
Measure D
Length of
burner tube
B65
Flange
Measure B
Burner tube
Measure C
Burner tube
Measure D
B55
B55
B55
B65
B65
B65
Standard 1
303
273
160
155
288
258
200
155
Standard 2
403
373
160
155
388
358
200
155
Standard 3
503
473
160
155
488
458
200
155
Burner
Oil capa-
city
Output
Recommended
Nozzle
Recommended
Pump pressure
kg/h
kW
Mcal/h
Angle
Type
Bar
B 55-2
14-67
166-795
143-685
45°, 60°
Solid, Semisolid
14
B 65-2
24-99
285-1174
246-1012
45°, 60°
Solid, Semisolid
14
The net caloriic value of 11,86 kWh/kg for light oil has been used.
3.4
Output range and nozzles recommended