COMMISSIONING CHARGE

When  commissioning  a  new  battery  (first
charge), follow procedure a) or b).
Procedure a) is recommended.
a) IU method (boost charge): 
At  a  raised  voltage  of  2.33  –  2.40  Vpc.  The
charging time will be 12 to 24 hours depen-
ding on the initial charge condition. The cur-
rent must be limited to 4 x I

10

.

Boost charging must be switched off or swit-
ched  over  to  float  charging  as  soon  as  the
fully charged state is reached.
b) Float charge: 
With a voltage of 2.25 Vpc. Full capacity  will
be obtained after a longer period of 4 to 6
weeks depending on state of charge.

STANDBY  OPERATION  / FLOAT

CHARGE

Float Voltage

The  recommended  float  /  charge  voltage
is  2.25  V  per  cell  at  20°C  (tolerance  2.23  –
2.25  Vpc).  The  charger  voltage  amounts  to 
2.25 Vpc x no. of cells. If the average ambient
temperature  deviates  more  than  ± 10°C
from the reference temperature of 20°C, it is 
recommended to adjust the float voltage to
the  following  temperature  compensation
curve:

Temperature

Float voltage

-10 °C

2,37 Vpc

0 °C

2,33 Vpc

10 °C

2,29 Vpc

20 °C

2,25 Vpc

30 °C

2,23 Vpc

40 °C

2,21 Vpc

In case that the average temperature
deviates less than ±5°C, no temperature
compensation has to be applied.
The recommended float charge voltage is
2.25  volts  per  cell  at  20°C.  Following  a 
commission  charge  and  after  6  months 
continuous  charge  at  the  recommended
float  voltage,  individual  cell  voltages  will
stabilise within ±4.5% of the mean applied
voltage.
However,  immediately  following  commis-
sioning  and  for  the  initial  6  months  of 
continuous  float  charge,  individual  cell
voltage  values  outside  the  above  tolerance
may  be  observed  without  adverse  efect.
There is no relationship between a cell’s float
voltage  and  its  discharge  capacity.  Cells  are
prefectly  capable  of  giving  their  discharge
capacity even when outside the ±4.5% range.
After 6 months service, should any individual
cell show a continuing reduction or increase
in  voltage  outside  the  above  limits  over 
3  successive  monthly  periods,    our  sales
department should be contacted for advice.

Charging Current

Limitation  of  the  charging  current  is  not
required  under  float  charge  condition  at 
2.25  Vpc.  At  higher  charge  voltages  the 
charge current shall be limited to 4 x I

10

.

Boost Charge

To reduce the recharge time the battery may
be recharged at 2.33 – 2.40 V per cell with a
current limited to 4 x I

10

. Fast charging must

be switched over to float charging  when the
fully charged state is reached.

Ripple Current

In the standby operation mode the effective
value  of  the  A.C.  ripple  current  must  not
exceed  5  A/100Ah  C10,  otherwise  reduced
operational life must be expected.

TEMPERATURE

The  recommended  operating  temperature
range is -10°C to +45°C. The battery will give
best performance and service life when wor-
king  in  the  temperature  range  of  +10°C  to
+30°C. Higher temperatures reduce the ope-
rational life. Lower temperatures reduce the
available capacity. Temporary peak tempera-
tures  shall  not  exceed  –30°C  and  +55°C.
Consideration must be given to depth of dis-
charge  (low  temperatures)  and  ventilation
(high temperatures). All technical data relates
to  the  rated  temperature  of  +20°C.  Do  not
expose cells to direct sunlight.

DISCHARGING

End of Discharge Voltage

The  battery  must  not  be  discharged  more
than the capacity specified in the performan-
ce tables. Deeper discharges may damage the
battery and shorten its operational life. As a
general  rule  the  end  of  discharge  voltage
shall be limited to the values listed below:

Discharge time

1h < t < 5h

1.70 Vpc

5h < t < 8h

1.75 Vpc

8h < t < 24h

1.80 Vpc

Individual cell voltages may fall below U

E

by

not  more  than  0.2  Vpc.  A  low  voltage  dis-
connect  is  recommended  to  prevent  deep
discharge.  Special  attention  should  be  given
to small loads that are not automatically dis-
connected at the end of discharge.

Discharged Cells and monoblocs

OPzV  batteries  must  not  be  left  in  a  discharged
condition  after  supplying  the  load  but  must  be
immediately returned to  recharge mode. Failure
to observe these conditions may result in greatly
reduced service life and unreliability.

Accidental Deep Discharge

Following accidental deep discharge, the batte-
ry must be recharged at 2.25 Vpc followed by
an equalizing charge. As the internal resistance
is high at first, the initial charge current is low.

Important notice:

Each  deep  discharge  is  abusive,  and  could
affect the life expectancy of the battery.

TESTING

Capacity tests are to be carried out in accor-
dance with EN 60896-2. Check that the bat-
tery is fully charged. Before testing new bat-
teries  it  must  be  ensured  that  a  sufficient
commissioning charge has been applied. 

Temperature correction factor

The temperature has an effect on the battery
capacity. The following  table shows the cor-
rection  factors  for  temperatures  other  than
the reference temperature of 20°C.

RECHARGE

After a discharge the battery can be recharged
at the operating voltage (float charge voltage).
Depending on the depth of discharge this may
take up to 3 days. To reduce the charging time
the recharging can be carried out with a boost
charge voltage of 2.33 to 2.40 Vpc (fast char-
ge).  The  recharging  times  are  dependent  on
the  depth  of  discharge  and  on  the  charging
current  available.  Generally,  10  to  20  hours
duration can be expected at charging currents
between 5A and 40A per 100Ah C

10

. Fast char-

ging  must  be  switched  over  to  float  charging
when the fully charged state is reached.

Equalising charge

Under  exceptional  circumstances  only,  e.g.
after  deep  discharges  or  after  repeated
inadequate  recharging,  an  equalising  charge
shall be carried out according to clause a) of
the commissioning charge paragraph or with
the following IUI characteristic:
Charge  at  increased  voltage  of  2.33  –  2.40
Vpc, then continue with a constant current of
1.5 A per 100 Ah C

10

during which individual

cell voltages can be allowed to rise to 2.60 –
2.65  Vpc  maximum.  The  charging  must  be
monitored.  The  charging  time  at  constant
current shall be 5 to 10 hours. 

MAINTENANCE/CHECKS

OPzV batteries are maintenance free, sealed,
lead acid batteries and do not have to be top-
ped up with water or electrolyte. The contai-
ners  and  lids  should  be  kept  dry  and  free
from dust. Cleaning must be undertaken with
a damp cotton cloth without man-made fib-
res or addition of cleaning agents. Avoid sta-
tic  discharges  generated  during  cleaning.
Every 6 months, check the total voltage at the
battery  terminals,  the  cell  voltages  of  pilot
cells  and  the  temperature.  Once  a  year,  in
addition to the above, take readings of indi-
vidual cell voltages. Keep a logbook in which
the measured values can be noted as well as
power  cuts,  discharge  tests,  etc.  Do  not
attempt to open the safety valve. Opening
could cause lasting damage to the battery
and is prohibited.

SPECIAL APPLICATIONS

Whenever  OPzV  batteries  are  to  be  used
for  special  applications  such  as  repeated
cycling  or  under  extreme  ambient  con-
ditions please contact your SALES OFFICE.
For  further  information  please  visit  our
website: www.enersys-emea.com

Discharge

Temperature in °C

Time

-10

0

+10

+20

+30

+40

5-12 hours

0.60 0.78 0.90

1.00

1.05

1.07

1-4 hours

0.55 0.74 0.88

1.00

1.06

1.08

End voltage

2

Capacity tests are to be carried out in accor-
dance  with  EN  60896-21/22.  Check  that  the
battery  is  fully  charged.  Before  testing  new
batteries it must be ensured that a sufficient
commissioning charge has been applied.

Summary of Contents for PowerSafe OPzV

Page 1: ...ion Operations and Maintenance Instructions Consignes d installation d exploitation et de maintenance Gebrauchsanweisung und Bedienungsanleitung Normas de instalaci n utilizaci n y mantenimiento RESER...

Page 2: ...re parts Application of additives to the electrolyte Unauthorised interference with the battery PowerSafe OPzV Installation operating and maintenance instructions ENGLISH No smoking no naked flames no...

Page 3: ...UE by not more than 0 2 Vpc A low voltage dis connect is recommended to prevent deep discharge Special attention should be given to small loads that are not automatically dis connected at the end of...

Page 4: ...e des temp ratures inacceptables Montage des l ments en parall le Les l ments OPzV peuvent tre connect s en parall le pour fournir une capacit plus lev e Pour ce type de montage utiliser uniquement de...

Page 5: ...harge 1h t 5h 1 70 V lement 5h t 8h 1 75 V lement 8h t 24h 1 80 V lement Les tensions individuelles ne doivent jamais tre inf rieures de plus de 0 2 V l ment par rapport la tension finale Une coupure...

Page 6: ...ef hrliche Spannung bei Spannungen 60Vdc Elektrolyt ist stark tzend Im normalen Betrieb ist Ber hrung mit dem Elektrolyten ausgeschlossen Bei Zerst rung der Geh use ist der freiwerdende gebundene Elek...

Page 7: ...ine Entlade str me die am Entladeende nicht automa tisch abgeschaltet werden Entladene Zellen Nach Entladungen auch Teilentladungen sind OPzV Batterien sofort aufzuladen Standzeiten im entladenen Zust...

Page 8: ...l o a los ojos Consultar a un m dico La ropa con cido debe lavarse con agua Seguir las instrucciones de uso Reciclar los componentes de la bater a Contiene plomo Aviso Riesgo de fuego explosi n o ince...

Page 9: ...carga debe limitarse a los valores siguientes Duraci n de la descarga Tensi n final 1h t 5h 1 70 V elemento 5h t 8h 1 75 V elemento 8h t 24h 1 80 V elemento Las tensiones individuales no deber n nunca...

Page 10: ...Notes...

Page 11: ......

Page 12: ...teway East Building Level 11 189721 Singapore Tel 65 6508 1780 2013 EnerSys All rights reserved Trademarks and logos are the property of EnerSys and its affiliates unless otherwise noted EnerSys EMEA...

Reviews: