1. Features ............................................................................................5
2. Technical Information .....................................................................5
3. Safety Precautions ..........................................................................6
4. Installation .......................................................................................6
5. Operating Instructions ...................................................................7
6. Fault codes.......................................................................................9
7. Service and Troubleshooting ........................................................9
1.1.
Microprocessor-controlled
1.2.
Able to auto identify battery’s capacity
1.3.
Able to adapt to State of Charge (SoC)
1.4.
Compatible with battery voltages of:
1ph
3ph
12V
24V
24/36/48V
36/48V
72/80V
96V
120V
1.5.
Unique profile for charging Thin Plate Pure Lead (TPPL)
1.6.
Unique profiles for NexSys
®
battery charge applications: NXBLOC;
NXSTND.
1.7.
Fully programmable to unique fleet requirements.
1.8.
Battery chemistry agnostic - TPPL, Flooded and Gel Lead Acid.
2.1. Name plate labels
2.1.1. Name plate label definitions
1. Features
TABLE OF CONTENTS
2. Technical Information
BATTERY CHARGER
INSTRUCTIONS FOR USE
ENGLISH
2
Item
Description
Serial Number
Provides date code.
Hertz
Input voltage frequency. Under no conditions operate
the charger at a different frequency or from a generator
with unstable frequency.
Phase
TCX. When “1” indicates a Single Phase Charger
and “3” indicates a Three Phase Charger.
AC Volts
Nominal voltage for which this charger is rated to operate.
DC Volts
Nominal DC output voltage of the charger
Modules
Actual number of power modules installed
in the charger cabinet.
DC Amps
DC current that this charger will deliver to a discharged
battery with the number of power modules installed
and based on the Nominal Voltage
2.1.2. Output power letter codes
Output Power
(kW)
Number
Modules
Module Power
(kW)
1.0
1
1.0
2.0
2
1.0
3.0
3
1.0
3.5
1
3.5
7.0
2
3.5
10.5
3
3.5
14.0
4
3.5
17.5
5
3.5
21.0
6
3.5
24.5
7
3.5
28.0
8
3.5
2.1.3. Cabinet size (number of modules available) and DC cable size
Phases
Module
Positions
Standard
Cable Gauge
Comments
1ph
Max 1
6 mm
2
stand alone cabinet
1ph
Max 3
25 mm
2
Three slot, 3 kW cabinet
3ph
Max 2
35 mm
2
Two slot, 7 kW cabinet
3ph
Max 4
70 mm
2
Four slot, 3.5 to 14 kW cabinet
3ph
Max 6
95 mm
2
Six slot, max 21 kW cabinet
3ph
Max 8
70 mm
2
or 1 x 95
mm
2
Eight slot, max 28 kW cabinet.
Dual cable for 24/36/48Vdc single
cable for 72/80Vdc