background image

4

www.enersys-emea.com

MAINTENANCE AND INSPECTION

The optimum maintenance and inspection procedure will vary considerably
according to the application, number and critical nature of installations,
along with other commercial considerations.

It is advised that, in addition to the instructions detailed below, the Battery
Record Sheet as shown in Appendix B is utilised.

MONTHLY INSPECTION

SIX- MONTHLY INSPECTION

ANNUAL INSPECTION

As with monthly and six-month checks, the type of annual inspection is
based on the critical nature of installations, along with other commercial
considerations i.e. feasibility of reduced autonomy, manpower availability
etc. One method of checking the state of health of the battery is to perform
a partial discharge using the actual system as the load.

Example

For a system with a back-up autonomy time of 1 hours:

Switch off the main power supply and allow the battery to supply the
required back-up power to the load.

After approximately 15 minutes* measure and note the terminal voltage of
the individual monoblocs and the corresponding string from which the
measurement was taken. An example of a battery record sheet is shown in
Appendix B.

After all of the monoblocs have had their terminal voltages measured, the
main power should be returned to the system.

By reference to the noted values on the record sheet calculate the average
monobloc terminal voltage for each individual string. 

From this value, calculate a voltage equating to 5% less than the average.
Monoblocs with a terminal voltage below the calculated value should be
considered for further monitoring or replacement to ensure maximum
system autonomy.

*The actual discharge duration is unimportant as the test is one of
comparison and does not have a specific pass/fail criteria. It should be
noted however that the longer the duration of the discharge is allowed to
continue before measurements are taken, the earlier it might be possible to
detect monoblocs prematurely failing.

It is only possible to check the actual capacity of the system battery by
performing a full discharge test on the battery to a known endpoint voltage.
Unfortunately, although this gives excellent battery maintenance cover,
it means that for a short period the battery will provide substantially
reduced autonomy. Hence this method should only be implemented during
times of complete system redundancy.

EnerSys

®

can design a tailor-made maintenance procedure when supplied

with the relevant information.

REJECT PROCEDURE AND DISPOSAL

REJECTION

Should a product, on receipt or otherwise, appear to be unserviceable
FIRST contact EnerSys detailing the circumstances.

Full details of date of shipment, commissioning records and all
maintenance records should be relayed.

DISPOSAL

All monoblocs for disposal should be shipped to a recognised scrap
recoverer, or regulated collection point.

EnerSys utilises a licensed reprocessor of lead and plastics. We will, at no
charge, dispose of batteries if they are delivered to our factory in Newport,
UK. Alternatively, please contact your local sales office who will be able to
assist with your disposal needs.

In the UK, this is a legal requirement and products should be disposed of in
accordance with the rules of the relevant Local Authority. The Local
Authority is required to maintain a list of their approved disposal and
recycling operators.

DO NOT INCINERATE END OF LIFE BATTERIES.

APPENDICIES

APPENDICIES

The following pages show the information listed below. If you have any
other requirements, please do not hesitate to contact our Sales Office or
your local agent.

APPENDIX A

THE DATASAFE

®

MX BATTERY RANGE - PRODUCT DETAILS

Notes- Weight is in Kg. A = Length; B = Width; C = Container; D = Height over terminals

Battery capacities increase with a higher temperature.

Unless otherwise stated all dimensions are in millimetres.

Battery Rating is measured in watts per cell at the 15 minute rate to
1.67 Volts per cell at 25°C.

For further information on any of our products, please contact our
Sales Office.

Measure total
battery voltage

1 Total battery
voltage on float
charge.

Adjust float
voltage as
specified in
Section 2

Recommended
float volts per cell
x number of cells
in series

Measure
individual
monobloc
voltages

2 Individual
monobloc
voltages on float
charge

Contact EnerSys

®

if non compliant

Within 5.0% of
the mean

Check for
damage or other
impairment

3 Appearance 

If a concern is
found check the
cause and replace
the monobloc as
necessary

Check for
contamination by
dust, etc.

4 Cleanliness

If contaminated
ISOLATE
monobloc and
clean with a
damp soft cloth

Check for
corrosion of the
cubicle, battery
stand, connecting
cables and
terminals

5 General
condition

Perform cleaning,
corrosion
prevention
treatment,
painting, etc.

WHAT TO

METHOD

REQUIREMENT

ACTION

INSPECT

Measure total
battery voltage

1 Total battery
voltage on float
charge.

Adjust float
voltage as
specified in
Section 2

Recommended
float volts per cell
x number of cells
in series

WHAT TO

METHOD

REQUIREMENT

ACTION

INSPECT

12mx150

12

150

250

97

140

152

9.0

M6

12mx200

12

207

250

97

191

204

12.5

M6

12mx270

12

270

220

121

245

256

17.5

M6

Product

Nominal

Dimensions

Typical

Terminal

Type

Voltage

Rating

A

B

C

D

Weight

Thread

Reviews: