2
www.enersys-emea.com
IMPORTANT
Please read this manual immediately on receipt of battery before
unpacking and installing. The installation and erection of batteries should
be undertaken by suitably qualified persons only. Failure to comply with
these instructions will render any warranties null and void.
CARE FOR YOUR SAFETY
Handling
DataSafe
®
MX batteries are supplied in a fully
charged state and must be unpacked carefully to
avoid very high short-circuit currents between
terminals of opposite polarity. Use care when
handling and moving batteries. Appropriate lifting
equipment must be used.
Keep flames away
In case of accidental overcharge, a flammable
gas can leak off the safety vent.
Discharge any possible static electricity from
clothes by touching an earth connected part.
Tools
Use tools with insulated handles.
Do not place or drop metal objects on the battery.
Remove rings, wristwatch and articles of clothing
with metal parts that may come into contact with
the battery terminals.
Dispose at registered
waste handling
facility
GENERAL GUIDELINES AND INFORMATION
HEALTH AND SAFETY
DataSafe MX batteries are electrically live at all times. Care must be taken
when handling the monoblocs, even when in a damaged or discharged
condition.
Always....
Remove all metal personal effects such as rings, metal watch bands,
belt buckles.
Switch off circuit before connecting or disconnecting battery.
Use insulated tools.
Keep sparks, flames and lighted cigarettes away from the battery.
Remember - batteries are heavy; use appropriate handling techniques.
Wear protective clothing, (eg., gloves, safety glasses, etc.)
Never....
Lift a battery by its terminals.
Charge in a sealed container.
Incinerate.
Short circuit.
Charge with a voltage greater than specified in this manual.
Storage
If the battery cannot be installed immediately, it should be stored in a
cool, clean and dry environment.
If the open circuit voltage drops to less than 2.09 Volts per cell, a
recharge will be necessary. The ambient temperature will affect the self
discharge and therefore the time between recharges.
Batteries should not be kept in a discharged condition.
TRANSPORTATION
DataSafe MX batteries are classed as ‘Non Hazardous’ for transportation by
air, sea or road. They may, therefore, be transported without restriction.
Notes- TREM Cards etc., provided the terminals are adequately protected
from short circuit. For air transportation ICAO (and IATA) special provision
A67 applies.
UNPACKING
On delivery, carefully examine the consignment for any obvious signs of
transit damage and then ensure that the goods are complete and agree
with the material list, advice note or invoice.
Monobloc terminal nuts and washers are normally packed in a sachet
inside the monobloc carton.
MONOBLOC CLEANLINESS
Please ensure that the monoblocs are clean at all times. Cleaning should be
carried out using a damp soft cloth.
Warning - Do NOT use any type of oil, solvent, detergent, petroleum-based
solvent or ammonia solution to clean the battery containers or lids. These
materials will cause permanent damage to the battery container and lid
and will invalidate the warranty.
No smoking, no naked flames,
no sparks
Electrolyte is corrosive
Clean all acid splash in eyes or on
skin with plenty of clean water.
Then seek medical help. Acid on
clothing is to be washed with water.
Danger
Warning: Risk of fire, explosion, or burns.
Do not disassemble, heat above 60ºC, or incinerate.
Avoid any short circuit. Metallic parts under voltage on the
battery, do not place tools or items on top of the battery
Other safety precautions that need to be taken
Battery must be
recycled
Protect eyes
from electrolyte
Read
instructions
Do not charge in
sealed container
Months on Shelf
0
1
2
3
4
5
6
7
8
9
10
11
12
State of charge (20°C)
100%
99%
97%
96%
95%
94%
93%
92%
91%
90%
90%
89%
88%
State of charge (30°C)
100%
97%
95%
93%
91%
90%
88%
86%
85%
84%
82%
81%
80%