Configuration 3: 

Recommended Grounding of SE41 RPN with Remote AC Service Disconnect located 

greater than four feet away from the SE41 cabinet 
 
Objective: 

Install a 

continuous

 length of #2AWG tinned solid copper conductor originating at the ACEG bus in the remote 

service disconnect enclosure and have it terminated at the Enclosure Master Ground Bar (MGB).  

Steps: 

1.

 

Connect the #2AWG tinned solid copper conductor to the ACEG bus in the remote service disconnect 
enclosure and then to the ground rod nearest to the AC service disconnect enclosure and continue 
this GEC to the driven ground rod of the SE41 system.  

2.

 

Connect the GEC to the SE41 driven ground rod nearest to the Enclosure MGB and have it terminated 
to the Enclosure MGB using an appropriate two-hole compression lug. (

refer to Figure 3

). 

Note:

 Avoid tight radius bends.

 

It is recommended that all buried grounding connectors are 12”

 

below  finished  grade  line  or  below  the  frost  line.

 

For  below  grade  connections,  crimp  or 

mechanical connectors may be used instead of an exothermic weld provided they are listed 
for direct burial applications.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Figure 3 

 SE41 RPN with remote disconnect (>4') grounding diagram

 