TECHNICAL ADVISORY BULLETIN 
Recommended Grounding for SE41 Remote Power Node Enclosure   

 
Date: 4/21/2020 
Model #: 

SE41 Remote Power Node Enclosure 

 

Issue 

 

As there are three different configurations of the SE41 RPN enclosure, additional information on 
grounding is required beyond what is provided in the installation manual.  

 

Corrective Action 

 

Provide grounding instructions with diagrams for the three different configurations of the SE41 RPN 
enclosure.  

 

The  grounding  specifications  and  diagrams  depicted  in  this  TAB  are  based  on  recommended 
industry best practices. However, site grounding design and construction shall always adhere to 
local electrical codes and the internal standards of the company that is responsible for ownership 
and operation of equipment. 
 

 

Warning  

 

Only  qualified  personal  should  install  and  connect  the  power  components  within  the  Alpha 
system. 

 

 

An enclosure that is not properly grounded presents an electrical hazard and will likely result in 
premature equipment failure.

  

 

A  proper  grounding  system  (i.e.  ground  electrode  system)  that  meets  or  exceeds  the 
specifications of the equipment must be designed and installed prior to or in conjunction with 

the installation. The ground system must be bonded to the enclosure to ensure a “common” or 
“single

-

point” 

ground.

 

 
 
 
 
 
 
 
 
 
 
 