3

017-950-B1-001, Rev. A (07/2020)

A/B [C/D] NEG

Black, Pin 5

Vbatt 3

A 36V

Red, Pin 9

Vbatt 2

A 24V

Orange, Pin 4

Vbatt 1

A 12V

Brown, Pin 10

+

-

3A

+

-

2A

Black (String -) 0V

+

-

1A

36VDC

Red (+)

2.0  Battery Installation and Wiring 

Load batteries into cabinet with the positive terminals (+) 

facing forward.  Coat the hardware and battery terminals 

with an approved battery terminal corrosion inhibitor such as 

NCP-2

®

 and assemble the cables and hardware as shown in 

the illustrations below.  Torque hardware to 110 in-lbs (12.4 

Nm).  If M6 hardware is used, torque to 120 in-lbs (15.6 Nm).

With a Midtronics

®

 Conductance meter (Celltron

®

 Essential, 

Celltron

®

 Advanced or equivalent) measure the conductance 

value (MHOS) of each battery and record for use in Section 

6.2 

Battery Configuration.  

Also, record the battery date code 

on the battery label for entry on the DATE SET screen.

To Battery Connector

To Precision Temperature Sensor (PTS) 

connector

To Smart  

AlphaGuard 

Connector

Verify battery voltage, cable color, connection 

and polarity are correct before proceeding. 

WARNING! ELECTRICAL HAZARD

Use 1/4-20 x 3/4" (19 mm) bolts for threaded insert terminals.  If using a spacer for the in-line fuse link, 

use 1/4-20 x 1" (25.4 mm) bolts.

 

CAUTION!

3.0 Output Voltage Reconfiguration Procedure

Tools Required: 

Small flat-blade screwdriver

1.  To access output voltage terminal, remove the Inverter Module. 

2.  Loosen the terminal screw and move the output voltage wire  

(Fig. 3-1) to the desired output voltage position on the terminal strip.

3.  Torque the terminal block screw to 7 in-lbs (0.79 Nm) to secure the 

output voltage wire.

4.  Reinstall the Inverter Module.

Fig. 2-1, Battery String Wiring Diagram

Fig. 3-1, Output Voltage Terminal Positions

63V   89V

Factory Default Setting, 89V

Alternate Setting, 63V

Tighten to 7 in-lbs (0.79 Nm)

Before performing this procedure, unplug the Power 

Supply from the AC power source and batteries.

WARNING! ELECTRICAL HAZARD

Fig. 2-2, Hardware Stack Up,  

Non-Fused Connection

3/4" (19 mm) x 

1/4-20 Bolt

Split Washer
Flat Washer

Battery Sense Cable 

or PTS

Battery Cable
Battery Terminal

Nut

Split Washer
Flat Washer

Battery 

Cable
In-Line Fuse Link

Flat Washer
1" (25.4 mm) or  

3/4" (19 mm) x 1/4-20 Bolt

1" (25.4 mm) x 

1/4-20 Bolt

Flat Washer

Split Washer

Spacer

Battery Terminal

Fuse

Fig. 2-3, Hardware Stack Up, Fused Connection

In-line 

Fuse

The battery terminal hardware is subject to change based on battery make and model.

NOTICE:

Summary of Contents for Alpha Broadband UPS

Page 1: ...e contains a ferroresonant transformer AC oil capacitor line isolation relay Power Distribution Module and EMC Filter board Intelligent Inverter Module Required for standby operations and contains cir...

Page 2: ...standard options Refer to the technical manual for additional details on advanced status monitoring using the SFP optical port The EMM supports the Smart Display functionality and provides the communi...

Page 3: ...d insert terminals If using a spacer for the in line fuse link use 1 4 20 x 1 25 4 mm bolts CAUTION 3 0 Output Voltage Reconfiguration Procedure Tools Required Small flat blade screwdriver 1 To access...

Page 4: ...nput and Output Voltage Current 2 Describes Power Supply Mode of Operation 3 Describes Status of Functions 4 Functionality top level menu PWR BATT COMM and APPS 5 Softkeys Menu driven system configura...

Page 5: ...m LED Normal Operation On Off Minor Alarm Flash Off Major Alarm Flash Flash Output Off Off Flash OUTPUT ALARM TEST A Self Test Fail alarm will be activated and appear on the Smart Display and Transpon...

Page 6: ...MS voltmeter to verify output Output voltages should appear within the ranges shown in Table 6 2 3 To halt cancel a self test in progress press and hold the TEST button for one to two seconds or chang...

Page 7: ...ress 192 168 100 1 into the web browser s address field 4 The transponder s web server home page will appear A Static IP address 192 168 100 2 may need to be set on your network interface card to conn...

Reviews: