6.0 Data Management, continued
55
704-939-B10-001 Rev. A5 (06/2019)
Table 6-4, Recommended Settings for Discrete Alarms, continued
Discrete Alarms for Optional Generator
Discrete Alarms
Description
Setting
genGeneratorStatus (1)
Generator OFF
Disable
genGeneratorStatus (2)
Generator Running (Test)
discreteMinor
genGeneratorStatus (3)
Generator Running
discreteMajor
genGeneratorStatus (4)
Generator Fail
discreteMajor
genGasHazard (1)
No Alarm
Disable
genGasHazard (2)
The concentration of hydrocarbon
fuel in the generator enclosure has
exceeded safe limits. Generator
operation is suspended. The alarm is
cleared when the sensor reports safe
conditions, and the alarm is reset via
the resetLatchedAlarms(3) command
found in the genEquipmentControl
MIB point.
discreteMajor
genWaterIntrusion (1)
No Alarm
Disable
genWaterIntrusion (2)
Water level within the generator or fuel
enclosure has exceeded safe limits
for generator operation. Generator
operation is suspended while this
alarm is active. The alarm resets when
the water returns to a safe level.
discreteMajor
genPadShear (1)
No Alarm
Disable
genPadShear (2)
Indicates that the generator or
fuel enclosure has shifted from
its mounting position. Generator
operation is suspended. The alarm
resets when the unit is returned to its
original position.
discreteMajor
genEnclosureDoor (1)
No Alarm
Disable
genEnclosureDoor (2)
Generator and/or auxiliary fuel
enclosure door is open
discreteMajor
genCharger (1)
No Alarm
Disable
genCharger (2)
Ignition battery charger is not
operating correctly
discreteMajor
genFuel (1)
No Alarm
Disable
genFuel (2)
Indicates the engine’s fuel supply is
insufficient for extended operation.
Alarm resets when fuel is replenished.
discreteMajor
genOil (1)
No Alarm
Disable
genOil (2)
Indicates the engine’s oil is inadequate
for safe operation. Alarm resets when
the condition returns to normal.
discreteMajor
genMinorAlarm (1)
No Alarm
Disable