January, 2005 – Operators Manual
ENERNET Corporation
11
“What are the buttons inside my thermostat for?”
Referring to Figure 7, the SW4 INSTALL button located at the
bottom center of the printed circuit board is used to put the
thermostat in the Install/Remove mode. The SW9 LINK button
located at the bottom far left of the circuit board and PB1 REMOVE
button above and to the right of SW9 are also used when installing or
removing an RCN from the thermostat. See the section entitled
INSTALLING AND REMOVING NODES. In many cases your
thermostat has come from the factory already linked to the control
node or a trained technician performed the linking procedure when
the T9000 was firsts installed. If you accidentally press the SW4
button and put the thermostat into the install mode, simply press it
again to put the thermostat back in normal operation. SW9 is only
used during installation. Pressing SW9 when not in the installation
mode has no effect. PB1 is only used when removing nodes that
have previously been linked to the thermostat.
(NOTE: Refer to the INSTALLING AND REMOVING NODES
section of this manual for detailed instructions. If you need
assistance installing or removing an RCN, contact your distributor
or call ENERNET Corporation for technical support.)
“I see solar cells on the T9000; does it need light to operate?”
When not reading temperature or communicating with an RCN, the
T9000 thermostat consumes very little power. Under some lighting
conditions, it will run off of the solar cells, even further extending
the lifetime of the batteries. While it’s a bad idea to let it get direct
sunlight, or be too close to a lamp, a well-lighted space is beneficial
to battery life.
“When my a/c turns off, I can’t immediately make it run again?”
This is normal. What you are experiencing is called an anti short-
cycle delay. Because of high pressure in the system, it’s not a good
idea to start your air conditioner immediately after it has just shut
down. The T9000 automatically prevents this from happening by
imposing a delay of approximately 3-minutes.
Summary of Contents for T9000
Page 15: ...January 2005 Operators Manual ENERNET Corporation 12 Figure 1 PTAC RCN Connection Diagram ...
Page 16: ...January 2005 Operators Manual ENERNET Corporation 13 Figure 2 J Box RCN Electric Heat Example ...
Page 17: ...January 2005 Operators Manual ENERNET Corporation 14 Figure 3 J Box RCN Fan Coil Example ...
Page 18: ...January 2005 Operators Manual ENERNET Corporation 15 Figure 4 Plug RCN Fan Coil Example ...