www.hi-velocity.com
Module RCM-I
RCM-I Installation
Specifications
RCM-I-70
RCM-I-100
Matching Fan Coil
HE-Z/HE-B/HE/HV-70/71
LV-70
HE-Z/HE-B/HE-P/HE/HV-100/101
Part Number
10090203070
10090203100
Tons
(1)
2.5 - 3.0
(8.8 - 10.6 Kw)
3.5 - 5.0
(12.3 - 17.6 Kw)
Refrigerant Type
R-410A
R-410A
TX Cooling MBH
(2)
30-36
(8.8-10.6 kW)
42-60
(12.3-17.6 kW)
Latent Cooling MBH
11.7 - 13.7
(3.4 - 4.0 kW)
16.0 - 22.2
(4.7 - 6.5 kW)
Fin Material
Aluminum
Aluminum
Tubing Material
Copper
Copper
Type of Fins
.006 Al
(0.1524mm)
.006 Al
(0.1524mm)
Hydronic
Connection
Sizes
Liquid Line (Lq)
1/2
”
(13mm)
1/2
”
(13mm)
Suction Line (S)
7/8
”
(22.3mm)
7/8
”
(22.3mm)
Drain Connection
3/4
”
M CPVC
(19mm)
3/4
”
M CPVC
(19mm)
Access Ports
Yes
Yes
Freeze Stat
Yes
Yes
Shipping Weight
34 lbs
(15.4 kg)
47 lbs
(21.31 kg)
Module Size (L x W x H)
19
3
⁄8
”
x 10
1
⁄8
”
x 18
1
⁄2
”
(492mm x 257mm x 470mm)
25
3
⁄8
”
x 10
1
⁄8
”
x 18
1
⁄2
”
(645mm x 257mm x 470mm)
RCM-I Specifications
Refrigerant Cooling Module
(2) Smaller condensers may be matched to the fan coil when needed (match TXV to condenser size)
(1) Minimum of
eight 2” outlets
per ton of cooling needed. (HE Duct = Minimum
four outlets
per ton)
MBH - Thousand British Thermal Units per Hour
TX - Thermal Expansion
TXV - Thermal Expansion Valve
Module RCM-I - RCM-I Coil Installation (6/8)