Accel CS Boiler - Gas Heat - Eighth Edition – January, 2015
20
BELOW GRADE SIDEWALL VENTING WITH POLYPROPYLENE – Snorkel style
2” or 3” non-concentric side wall vent termination, snorkel style.
VENTING GUIDELINES WHEN USING TWO PIPES (SNORKEL STYLE)
1. Use a properly installed window well (no window present) or equivalently constructed well with adequate drainage
2. Wall penetration must be at least 5” above the bottom of the window well.
3. Vertical rise must be limited to 4 feet maximum between elbows (see figure below); longer runs may require a
chimney chase and/or insulation on the vent to prevent condensation and freezing.
4. Vertical Separation: The exhaust vent must be above the air inlet between 12” and 15”.
5. Horizontal Separation: The horizontal distance between the air inlet and the exhaust vent must be a minimum of 4”
center to center.
Summary of Contents for EK1C
Page 60: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 59 DRAWINGS WIRING...
Page 61: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 60 DRAWINGS WIRING...
Page 62: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 61 DRAWINGS WIRING...
Page 63: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 62 DRAWINGS WIRING...
Page 64: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 63 DRAWINGS WIRING...
Page 65: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 64 DRAWINGS WIRING...
Page 66: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 65 DRAWINGS WIRING...
Page 71: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 70...
Page 72: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 71 THIS IS A BLANK PAGE...