background image

3

2.2 PE Connection and Leakage Current

PV System Residual Current Factors

-

In every PV installation, several elements contribute to the current leakage to protective earth (PE). these
elements can be divided into two main types.

-

Capacitive discharge current - Discharge current is generated mainly by the parasitic capacitance of the PV
modules to PE. The module type, the environmental conditions (rain, humidity) and even the distance of the
modules from the roof can effect the discharge current. Other factors that may contribute to the parasitic
capacitance are the inverter’s internal capacitance to PE and external protection elements such as lighting
protection.

-

During operation, the DC bus is connected to the alternating current grid via the inverter. Thus, a portion of
the alternating voltage amplitude arrives at the DC bus. The fluctuating voltage constantly changes the
charge state of the parasitic PV capacitor (i.e capacitance to PE). This is associated with a displacement
current, which is proportional to the capacitance and the applied voltage amplitude.

-

Residual current - if there is a fault, such as defective insulation, where an energized cable comes into
contact with a grounded person, an additional current flow, known as a residual current.

Residual Current Device (RCD)

-

All Energizer Force S Series inverters incorporate a certified internal RCD (Residual Current Device) to
protect against possible electrocution in case of a malfunction of the PV array, cables or inverter (DC). The
RCD in the Energizer Force S Series inverter can detect leakage on the DC side. There are 2 trip thresholds
for the RCD as required by the DIN VDE 0126-1-1 standard. A low threshold is used to protect against rapid
changes in leakage typical of direct contact by people. A higher threshold is used for slowly rising leakage
currents, to limit the current in grounding conductors for the safety. The default value for higher speed
personal protection is 30mA, and 300mA per unit for lower speed fire safety.

Installation and Selection of an External RCD device

-

An external RCD is required in some countries. The installer must check which type of RCD is required by
the specific local electric codes. Installation of an RCD must always be conducted in accordance with local
codes and standards. Energizer Force S Series recommends the use of a type-A RCD. Unless a lower value
is required by the specific local electric codes, Energizer Force S Series suggests an RCD value between
100mA and 300mA.

-

In installations where the local electric code requires an RCD with a lower leakage setting, the discharge
current might result in nuisance tripping of the external RCD. The following steps are recommended to avoid
nuisance tripping of the external RCD:

1. Selecting the appropriate RCD is important for correct operation of the installation. An RCD with a rating of
30mA may actually trip at a leakage as 15mA (according to IEC 61008). High quality RCDs will typically trip at a
value closer to their rating.
2. Configure the trip current of the inverter’ internal RCD to a lower value than the trip current of the external RCD.
The internal RCD will trip if the current is higher than the allowed current, but because the internal inverter RCD
automatically resets when the residual currents are low it saves the manual reset.

2.3 Surge Protection Devices (SPDs) for PV Installation

WARNING!
Over-voltage protection with surge arresters should be provided when the PV power system is installed. The
grid connected inverter is not fitted with SPDs in both PV input side and mains side.
Lightning will cause damage either from a direct strike or from surges due to a nearby strike.

Summary of Contents for Force 10.5S

Page 1: ...Installer Manual This guide describes how to use and install Energizer Solar Inverters To prevent improper operation before use please carefully read this manual FORCE S SERIES GRID TIED INVERTERS...

Page 2: ...AC Output 6 4 3 Efficiency Safety and Protection 7 4 4 General Data 7 5 Installation 8 5 1 Packing List 8 5 2 Preparation 8 5 3 Installation Space Required 9 5 4 Tools Required 9 5 5 Installation Ste...

Page 3: ...appear in this document as described below Danger Danger indicates a hazardous situation which if not avoided will result in death or serious injury Warning Warning indicates a hazardous situation whi...

Page 4: ...y and shock hazards or equipment damage Before connecting the inverter to the power distribution grid contact the local power distribution grid company to get appropriate approvals This connection mus...

Page 5: ...ypical of direct contact by people A higher threshold is used for slowly rising leakage currents to limit the current in grounding conductors for the safety The default value for higher speed personal...

Page 6: ...he consumer s cutout located between the inverter and the meter distribution system SPD test impulse D1 for signal line according to EN 61632 1 All DC cables should be installed to provide as short a...

Page 7: ...m Description A DC Switch Optional B PV1 C PV2 D PV3 E WiFi GPRS 4G USB F Waterproof Lock Valve G Communication Port H AC Connector I Grounding Screw Note Only authorized personnel are permitted to se...

Page 8: ...18 18 18 Start up voltage V 120 120 120 120 120 No of MPP trackers 3 3 3 3 3 Strings per MPP tracker 1 1 1 1 1 Max Inverter backfeed current to the array mA 0 4 2 AC Output Model Energizer Force 7S E...

Page 9: ...e Model Energizer Force 7S Energizer Force 8S Energizer Force 9S Energizer Force 10S Energizer Force 10 5S MPPT efficiency 99 00 99 00 99 00 99 00 99 00 Euro efficiency 97 40 97 40 97 40 97 40 97 40 M...

Page 10: ...re the air flow around the inverter is not blocked Do not install in places where gas or flammable substances may be present Avoid electromagnetic interference that can compromise the correct operatio...

Page 11: ...n Steps Step 1 Fix the bracket on the wall Choose the place you want to install the inverter Place the bracket on the wall and mark the position of the 3 holes from bracket Drill holes with electric d...

Page 12: ...ected should be less than 600V and operating voltage should be within the MPPT voltage range Note Please choose a suitable external DC switch if the inverter does not have a built in DC switch Warning...

Page 13: ...n contact by using a crimping plier Put the pin contact with striped cable into the corresponding crimping pliers and crimp the contact Insert pin contact through the cable nut to assemble into back o...

Page 14: ...LD NOT be connected with the inverter directly Step 3 AC Wiring Check the grid voltage and compare with the permitted voltage range refer to technical data Disconnect the circuit breaker from all the...

Page 15: ...nlock tool and pull it out or unscrew the threaded sleeve then pull it out 5 7 Earth Connection Screw the ground screw with screwdriver as shown below 5 8 Communication Device Installation This series...

Page 16: ...refer to the WiFi product manual for more details 5 Set up the site account on the monitoring platform please refer to the monitoring user manual for more details Export limitation setting Short pres...

Page 17: ...functionality To use this function a power meter or a CT must be installed For Meter installation please install it on the grid side DRM0 ESTOP Note For a precise reading and control of power a meter...

Page 18: ...pport team to get the latest firmware and copy the files to U disk using the following file path Master Update master xxx_Master_Vx xx hex Slave Update slave xxx_Slave_Vx xx hex Manager Update manager...

Page 19: ...and insert the monitoring device e T u r n on the DC switch or connect the PV connector to power on the inverter to finish the upgrade process Isolation Fault Australia Market Only This inverter comp...

Page 20: ...voltage display will indicate the Waiting status and green LED will flash Checking Inverter will check DC input environment automatically when DC input voltage from the PV panels exceeds 120V and PV...

Page 21: ...sword then press the button one time until it show Safety then long press the button to enter the option list Check Firmware version Region code and Power Quality Response Modes Please refer to the se...

Page 22: ...er to the unit must be turned on only after installation work has been completed All electrical connections must be carried out by qualified personnel in accordance with legislation in force in the co...

Page 23: ...he information of the inverter B Indicator LED Red The inverter is in fault mode C Green The inverter is in normal state D Touch Key The touch key is used to set the LCD to display different parameter...

Page 24: ...ek help from us if it does not go back to normal state GFC Fault Disconnect DC and AC connector check the surrounding equipment on the AC side Reconnect the input connector and check the state of inve...

Page 25: ...back to normal PLL Fault System will reconnect if the utility is back to normal Or seek help from us if it does not go back to normal state PV OVP Check the panel s open circuit voltage whether the va...

Page 26: ...e Maintenance Safety check A safety check should be performed at least every 12 months by a qualified technician who has adequate training knowledge and practical experience to perform these tests The...

Page 27: ...hat meets the following requirements Suitable for loads more than 30 kg Contains a handle Can be fully closed 8 3 Storage and Transportation Store the inverter in dry place where ambient temperatures...

Page 28: ...26...

Page 29: ...3000 Australia 8 Star Energy ESS Limited The Black Church St Mary s Place Dublin DO7 P4AX Ireland Phone 61 1300 757 827 Email hello energizersolar com Website www energizersolar com 2022 Energizer En...

Reviews: