Figure 12 Schematic diagram of electrical 

connection 

 

  If  one  set  of  arrays  is  connected  to 

another  with  the  opposite  polarity,  it 
will  cause  irreparable  damage  to  the 

product. Before connecting in parallel, be sure to 
confirm the voltage and polarity of each column. 
If  the  measurement  finds  that  the  polarity 
between  the  columns  is  reversed  or  the  voltage 
difference  is  greater  than  10V,  you  must  check 
the structure and configuration before making the 
connection. 

  The  number  of  photovoltaic  modules  in  series 

and  parallel  must  be  designed  reasonably 
according to the system configuration. 

  Photovoltaic  modules  of  different  electrical 

performance  models  cannot  be  connected  in  a 
string. 

  Special  solar  cables  and  connectors  should  be 

used  in  the  system,  and  all  connections  should 
be securely tightened. The cable size should be 
4mm2 (12 AWG) and must be able to withstand 

the  maximum  open  circuit  voltage  of  the 
photovoltaic system. 

  When  the  cable  is  fixed  on  the  bracket,  it  is 

necessary  to  avoid  mechanical  damage  to  the 
cable  or  photovoltaic  module,  and  do  not  press 
the cable with force. To fix the cable through the 
proper  way,  a  specially  designed  tying  coil  and 
wire  clip  must  be  used  to  fix  it  on  the  bracket. 
Avoid direct sunlight and water soaking cables. 

  Please  keep  the  connector  dry  and  clean,  and 

make  sure  that  the  nut  of  the  connector  is 
tightened before connecting. Do not connect the 
connector when it is found that the connector is 
wet, dirty, or in other bad conditions. Avoid direct 
sunlight and immersion of the connector in water. 
Avoid the connector falling on the ground or roof. 

  When  the  photovoltaic  module  is  in  a  live  state, 

please  do  not  plug  or  unplug  the  connector. 
When  it  is  necessary  to  open  the  connector, 
ensure  that  the  photovoltaic  module  is  in  a 
non-working  state,  and  must  use  professional 
unlocking tools and safety protection measures. It 
is  forbidden  to  pull  or  damage  the  locking 
structure. 

  The  junction  box  of  the  photovoltaic  module 

contains  bypass  diodes  connected  in  parallel  to 
the battery string of the photovoltaic module. The 
bypass  diode  in  the  junction  box  can  avoid  the 
degradation of photovoltaic module performance 
caused  by  shading  or  covering.  Please  refer  to 
the junction box diode specifications provided in 
the relevant product specifications. 

  When a local hot spot phenomenon occurs due to 

partial  shading  or  covering  of  the  photovoltaic 
module, the diode in the junction box will start to 
work, so that the photovoltaic module current will 
no longer flow through the hot spot cell, thereby 
limiting the heating and performance loss of the 
photovoltaic  module.  When  you  suspect  or  find 
that the diode is malfunctioning, please contact 8 

Summary of Contents for Beam Series

Page 1: ...ilicon PV Modules Installation Manual Version 1 0 Released in November 2021 This guide describes how to install the Energizer Solar Beam crystalline silicon PV modules To prevent improper operation be...

Page 2: ...nergy ESS Ltd The Black Church St Mary s Place Dublin DO7 P4AX Ireland 1 Table of contents 1 Table of contents 2 2 Important notes 3 3 Laws and regulations 3 4 Safety measures 3 5 Handling and unpacki...

Page 3: ...ntrol of 8 Star Energy Proprietary Limited hereafter 8 Star Energy this manual does not have any warranty meaning whether express or implied 8 Star Energy will not be responsible for any form of injur...

Page 4: ...ive oil bone setting water thinner adhesive sheets that can generate oxime gas and potting glue only for connectors Such as KE200 CX 200 chemlok etc TBP plasticizer detergent etc to avoid chemical dam...

Page 5: ...voltaic module and the installation surface should be kept to prevent the installation surface from touching the junction box When installing on the roof comply with the fire protection requirements o...

Page 6: ...he original packaging box before installation Please protect the packaging from damage It is necessary to protect the safety of photovoltaic modules when unloading especially when hoisting roof projec...

Page 7: ...e system design requirements the color of photovoltaic modules in the same row or square array should be the same 6 Mechanical installation 6 1 Installation conditions Recommended ambient temperature...

Page 8: ...a third party testing organization with static mechanical analysis capabilities to meet the country region or corresponding international standards The photovoltaic module must be firmly fixed on the...

Page 9: ...gure 4 or Figure 5 The 400mm pitch mounting hole size is 7x10mm and 4 x M6 stainless steel bolts are required Figure 5 Secure each bolt to the frame with stainless steel washers one for each side of t...

Page 10: ...ar PV modules otherwise this may affect the modules operation or performance Be sure to avoid shadowing effects from the module clamps Weep holes on the module frame must not be closed or obscured by...

Page 11: ...stallation method Figure 2 3 Fig 4 Fig 7 Fig 8 Fig 5 ENSP60M1 ENSP60M1 BL 1755 1038 30 1765 1048 35 1755 1038 30 1765 1048 35 5400Pa 2400Pa 5400 2400Pa Installation scope 400 50mm 1800 1800Pa Installa...

Page 12: ...nditions a photovoltaic module is likely to experience conditions that produce more current and or voltage than reported at standard test conditions Accordingly the value of Isc marked on this module...

Page 13: ...ng coil and wire clip must be used to fix it on the bracket Avoid direct sunlight and water soaking cables Please keep the connector dry and clean and make sure that the nut of the connector is tighte...

Page 14: ...Note that the copper wire cannot be attached directly to the aluminum Put the bolt through the cut washer and then through the hole in the aluminum frame Add the spring washer and nut on the other si...

Page 15: ...t necessary to clean the PV module rain will have a self cleaning effect If there is a lot of dirt on the surface of the photovoltaic module which has seriously affected the power generation use water...

Reviews: