background image

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 
 

 

 
 
 

 
 

 

 

Vented Installation

 

HYDRAULIC CONNECTIONS 

 

Procedures for the hydraulic connection of the circuit: 

a)

 

Connect  the  water  inflow  and  outflow  of  the  equipment  with 
tubing  or  joints  capable  of  supporting  a  combined 
temperature/pressure  of  a  constant  75°C  /  7  bar.  For  such  we 
recommend  the  use  of  tubing  which  is  resistant  to  high 
temperatures and pressures, such as  PEX, PPR, MULTICAMADA, 
among others. 

b)

 

A safety  valve needs to  be installed at the cold water inflow  of 
the  equipment.  The safety device should comply with standard 
EN

 

1487:2002, maximum pressure of 7 bar (0.7 MPa) 

c)

 

In addition to this device other components need to be installed 
to  guarantee  the  interruption  of  the  hydraulic  load,  in  the 
following order: 

 

Reflux valve 

 

Pressure reducing valve (in the event the pressure of 
the cold water inflow is greater than 4.5 bar) 

 

Safety/exhaust valve 

 

Expansion vessel 

 

The safety/exhaust valve should be connected by tubing with a 
diameter which is never less than the cold water inflow connection. 
The  part of the exhaust should  be connected to an interceptor, or, in 
the event this is inviable, raised at least 20mm above the floor to allow 
for visual inspection. 
All the above recommendations are to guarantee the safety of people, 
animals and others. 

SolarBox may be installed in tanks with two or more connections. The 
diagrams below illustrate two types of connection to a tank: 

 

PURGE HYDRAULIC CIRCUIT 

 

“y” FILTER 

After  doing  the  correct  installation  of  the  system,  the  installer  must 
purge all the hydraulic circuit before turning on the Solar Box. 

a)

 

Ensure that the valve 1a is closed 

b)

 

Close de valve 1b 

c)

 

Open the bleed valve inside the Solar Box 

d)

 

Open the discharge valve (drain) 7 

e)

 

Open valve 1a 

f)

 

Close the bleed valve inside the Solar Box (only when there is 
water with no bubbles leaving the valve) 

g)

 

Close the valve 1c (only when there is water with no bubbles 
leaving the valve) 

h)

 

Open the valve 1b 

i)

 

Turn-on the Solar Box 

HYDRAULIC CONNECTIONS 

 

Tank with more than two connections 

WARNING

 

The equipment is supplied with a 
“y”  filter  placed  on  the  SolarBox 
hydraulic  return  line,  at  the 
entrance of the heat exchanger.

 

 

 

WARNING/DANGER 

The  water  used  may  contain  impurities  and/or  substances  which 
are harmful to the system and to the health. Check the water being 
used  is  of  an  acceptable  quality  for  domestic  consumption.  The 
table below illustrates certain  parameters beyond which the water 
should be subjected to chemical treatment.  
 

Hardness (ºdH) 

pH 

Treatment 

3.0 to 20.0 

6.5 to 8.5 

No 

3.0 to 20.0 

<6.5 or >8.5 

Yes  

<3.0 or >20.0 

-------------- 

Yes  

 

Tank with two connections 

Tank with backup connections 

Legend:

 

 

1  Open/closed Valve 

Drain 

2  Non return Valve 

Mains Water 

3  Pressure Reducing Valve 

Hot Water Outlet 

4  Security Group 

SolarBox 

5  Expansion Vessel 

Thermodynamic Panel 

6  Filter 

S1 

Temperature Probe 

 

Summary of Contents for SolarBox

Page 1: ...e difference caused by the aforementioned external agents ensures the Klea ecological refrigerant fluid evaporates inside the solar panel The absence of glass in the panel ensures increased heat excha...

Page 2: ...he nuts corresponding to the four M6 flanged screws included in the packaging 2 Screw in the screws leaving a distance of approximately 3mm between the wall and the flange of the screw 3 Align the Sol...

Page 3: ...pump and gauges duly adpated for R134a fluid b Only use a vacuum pump to remove the air and moisture existing in the tube c Never use the system coolant to bleed the connection tubes d Keep the stop v...

Page 4: ...connections The diagrams below illustrate two types of connection to a tank PURGE HYDRAULIC CIRCUIT y FILTER After doing the correct installation of the system the installer must purge all the hydraul...

Page 5: ...is signaled by the led L9 blinking 3 Visualizations The display shows L4 ON C01 1 Auto mode ON configuration L1 Blinking when timer T01 run compressor timer L6 Blinking when timer T02 run error LP ti...

Page 6: ...U Wait about 5 seconds or push the K1 button WARNING The admission to this Menu is only for INSTALLERS or EXPERT PERSONNEL because parameters changes could damage the product or could make the product...

Page 7: ...ircuit Check the state of the hydraulic circuit Water leaking from the safety valve Absence of or incorrectly sized expansion tank if the leak is intermittent Installation and or correct sizing of exp...

Page 8: ...h manufacturer instructions or if there has been any form of intervention by unauthorized technicians has the appearance of modifications and or if the series number appears to have been removed or er...

Reviews: