46
MONOBLOC 100L
English
The water you use may contain impurities and/or substances damaging to the system and even harm-
ful to your health. Make sure you use water with quality fitting for home consumption. The following
table indicates some parameters according to which water must be subjected to chemical treatment.
Dureza(
0
dH)
pH
Tratamento
3,0 up to 20,0
6,5 up to 8,5
Não
3,0 up to 20,0
<6,5 up to >8,5
Sim
<3,0 or >20,0
-----------------
Sim
WARNING / DANGER
4.5. Condensates
During operation, condensation may occur. These condensates are collected in the drip tray and drained
through a hole at the back of the tray. The installer must connect the condensate hose supplied by the
manufacturer and direct the condensates to the drainage system or drainage siphon.
The condensate hose must not be bent/pressed and must be placed where it best
suits the proper flow of condensates.
Description
Cable
Type
Protection
Power cable
3G 1.5 mm2
H05VV-F
- Bipolar circuit-breaker 16A;
- Protection differential circuit breaker of30 mA;
4.6. Electric Connections
The device is supplied with a power cable.
It is advisable to make an electrical installation’s management to check its compliance with the current
standards. Make sure that the installation is proper to the maximum potential absorbed by the Heat Pump
(data query on the plate), not only on the cables section but also on its accordance to the current regu-
lation.
Multiple power outlets, electrical extensions and adaptors are forbidden. Land connection is mandatory. It
is forbidden to use the hydric, heating or gas systems pipes, to make the device’s land connection.
Before the first recommissioning, make sure that the main voltage is in accordance with the value on the
device’s plate. The producer may not be considered responsible for possible damages due to the lack of
land connection of the system or defect on power supply.
To turn off the device of the network, must be used the bipolar power switch according to the current rules
of CEI-EN (opening the contacts of, at least, 3 mm, better if equipped with fuses). The device’s connection
has to respect the European and national rules, and must be protected by a differential switch of 30 mA.
WARNING
Technical Manual
Summary of Contents for MONOBLOC 100esm
Page 2: ......
Page 4: ...4 MONOBLOC 100L Manual T cnico Portugu s...
Page 30: ...30 MONOBLOC 100L Manual T cnico...
Page 32: ...32 MONOBLOC 100L English Technical Manual...
Page 58: ...58 MONOBLOC 100L...
Page 60: ...60 MONOBLOC 100L Espa ol Manual T cnico...
Page 86: ...Notas Notes Notas...
Page 87: ...Notas Notes Notas...
Page 88: ...Notas Notes Notas...
Page 89: ...Notas Notes Notas...
Page 90: ...Notas Notes Notas...
Page 91: ......