background image

13

Operating Instructions and Owner’s Manual

 | Gas-Fired Low-Intensity Infrared Heater

The seams along the length of the piping and the joints between
sections of piping should be sealed to prevent a potential
leakage of flue gas into building. Use 100% RTV Silicone Rubber
Adhesive sealant suitable for 500°F.

6. All portions of the vent pipe shall be supported to prevent

from sagging.

7.

When the vent pipe passes through areas where the ambient

temperature is likely to induce condensation of the flue gasses,
the vent pipe should be insulated and a condensation drain
should be provided.

8. The minimum clearance to combustible materials for single-

wall flue pipe shall be 6 inches. This may be reduced when the
combustible material is protected as specified in the National
Fuel Gas Code or the authority having jurisdiction.

9.

Single-wall metal pipe shall not originate in any unoccupied

attic or concealed space and shall not pass through any attic,
inside wall or concealed space, or through any floor.

10. A venting system shall terminate at least 3 feet (0.9m) above

any forced air inlet located within 10 feet (3.1m).

b) Vent Termination

 (Residential Installations)

1. The vent terminal shall terminate above the roof line so that no

discharge opening is less than 2 feet (0.6m) horizontally from
the roof surface. The lowest discharge opening will be no closer
than the minimum height specified in the following table.
These minimum heights may be used provided the vent is not
less than 8 feet (2.4m) from any vertical wall or similar
obstruction.

BASIC FLUE VENTING (Residential Only)

Venting must be in compliance with the latest edition of the

National Fuel Gas Code (ANSI. Z223.1 latest edition: or the
authority having jurisdiction.

Uninsulated single-wall metal pipe shall not be used outdoors in

cold climates for venting of these heaters as specified by Section
7.8 of the ANSI Z223.1/NFPA 54 National Fuel Gas Code-latest
edition.

For the installation of a single-wall metal pipe through an exterior

combustible wall, refer to the latest edition of the National Fuel
Gas Code or the authority having jurisdiction.

In regions of the country where prevailing winds are consistently

higher than 40 mph, it may be necessary to terminate the vent
system above the roof level.

Other venting references can be found in equipment volume of the
ASHRAE Handbook.

A. SINGLE HEATER VENTING

a) Vertical Through the Roof

NOTE: For residential applications, the heater must

not be connected to a separate chimney,
but must be installed using the venting
system as specified below.

1. When venting the heater to outside of building through a roof,

use 3 inch O.D. single-wall metal pipe. This is to be constructed
of galvanized sheet metal or other approved noncombustible,
corrosion-resistant material as indicated by state and/or local
codes.

2. A vent passing through a combustible roof shall extend through

a 2-inch clearance roof thimble. Double-wall, Type B vent must be
used for the portion of the vent system which passes through
the roof. An approved vent cap (such as Leslie “VersaCap” Type
B) must be attached to the end of the flue.

3. The maximum equivalent length of vent pipe should be carefully

observed. A safety switch in the heater is designed to shut the
heater off before excessive flue restriction causes bad
combustion.

Minimum Equivalent Length = 5 feet of Pipe

Maximum Equivalent Length = 25 feet of Pipe

Use the following correction factors to obtain the equivalent length:

a) A horizontal run is equal to 15 feet of vent length.

b) An approved vent cap is equal to 10 feet of vent length.

c) For each elbow in the first 15 feet of run, they are equal to   
    10 feet of vent length.
d) For  each elbow past the first 15 feet of run, they are equal to 
      15 feet of vent length.

4. Limit the quantity of 90° elbows to two. When vent pipe is in a

horizontal run, it must rise not less than ¼ inch per foot from
the start of the vent system towards the vent terminal.

5. Joints between sections of piping shall be fastened by sheet

metal screws or other approved means.

SINGLE HEATER VENTING

Vent Cap

(Leslie VersaCap)

Type B

2' Min.

2' Min.

(when no wall or

parapet exist)

10'

or less

Flashing

2" Clearance Thimble

Seal joint &
annular space.

4"

Vent

Dia.

Total Vent

Height

(5' Min.)

¼ per ft. rise

Lateral

VERTICAL

THROUGH THE ROOF

2' Min.

(when no wall or

parapet  exist)

H (Min.)

Not less than 8ft.

2ft. min.

ll

a

W l

aci

tr

eV

  for an approved vent cap you have ---------10 ft.

  for a horizontal run you have -----------------15 ft.

Your Maximum Equivalent Length is ---------------- 25 ft.

EXAMPLE

Enerco Group, Inc.,  

Summary of Contents for HEATSTAR HST 45

Page 1: ...service must be performed by a qualified installer service agency or the gas supplier If you cannot reach your gas supplier call the Fire Department Gas Fired Low Intensity Infrared Heaters approved f...

Page 2: ...e conformer aux precautions et aux instructions a fourni avec cet appareil de chauffage avoir pour resultat la mort blessure et la perte de propriete ou les dommages physiques serieuses du danger de f...

Page 3: ...er of body oils from the hands to the surface of the reflector VentKit F102840 1 2 3 x 2 Pipe 26GA 2 1 36 x 3 B Vent 3 1 Gas Vent Top 3 4 1 Adj Wall Thimble 5 1 Storm Collar 6 1 3 Elbow 7 1 Adj Roof F...

Page 4: ...iant energy downward to the space to be heated Heat Exchanger A U shaped tube through which the heated products of combustion pass Rear Movable Hanger Provides support for the heat exchanger and refle...

Page 5: ...Hz single phase 1 amp Connection 3pinmoldedplug Gas Inlet Connection Connection Male NPT Gas Inlet Pressure The minimum inlet gas supply pressure for the purpose of input adjustment Natural Gas Minimu...

Page 6: ...HSTtube heater Specifiesthenationalstandardsandapplicablecodes that apply to the gas electric and venting requirements Specifies the national standards and applicable codes that apply to non resident...

Page 7: ...the floor Minimum required safe distances to combustibles must be maintained from vehicles parked below the heater When installed over hoists the minimum required safe distances to combustible must b...

Page 8: ...ose Location for Heater When selecting a suitable mounting location for the MHT HSTtube heater it is important to consider the following 1 The heater must meet the minimum mounting height requirement...

Page 9: ...s when stored under this heater will be subjected to radiant heat and could be seriously damaged 4 All horizontal venting sections must slope away from the heater at a rate of per foot 5 The total len...

Page 10: ...d through the roof be sure to carefully review the roof option installa tion portion of this section Ensure that the selected mounting site will satisfy the measurement param eters vent length not to...

Page 11: ...e tube ends extend through the flanges to help with alignment 3 Using the four long and four short nuts from the bolt kit 02876 secure the tube set to the burner box As shown in the diagram use the fo...

Page 12: ...current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved d...

Page 13: ...re consistently higher than 40 mph it may be necessary to terminate the vent system above the roof level Other venting references can be found in equipment volume of the ASHRAE Handbook A SINGLE HEATE...

Page 14: ...approved noncombustible corrosion resistant material as indicated by state and or local codes 2 For horizontal venting the vent lengths may be as follows Minimum Equivalent Length 5 feet of Pipe Maxi...

Page 15: ...problem the flue length should be shortened or insulated g For vent specifications all of the following conditions must be met The maximum equivalent length of vent pipe should be carefully observed A...

Page 16: ...Adequate clearances around the perforated fresh air plate must be maintained at all times In larger open areas of buildings infiltration normally is adequate to provide air for combustion DirectOutsid...

Page 17: ...Use wrought iron or wrought steel pipe and malleable iron fittings The use of copper tube and brass fittings is acceptable WARNING Electrical Shock Hazard Plugheaterinto groundedthreeprongceilingrecep...

Page 18: ...Use LP resistant joint compound on all threads 4 Check the pipe and tube connections for leaks before placing heating equipment into service When checking for gas leaks use a soap and water solution...

Page 19: ...ur 8 Periodic visual check of burner flame while unit is in operation through sight glass in bottom of unit Section 6 MAINTENANCE Pre Season Maintenance Heater area to be kept clear and free form comb...

Page 20: ...iter spark gap incorrect Try This Unplug heater power cord from the electrical outlet wait for a minimum of five seconds Plug heater cord back into outlet Unplug heater power cord from the electrical...

Page 21: ...equirements contact the gas company Check for 24V across valve terminals Check Shutoff On Valve IF NO Check wiring between the ignition module and the valve Repair replace wires as required If wiring...

Page 22: ...rs on the illustrations are keyed to the associated parts list E ITEM PART NUMBER DESCRIPTION MHT 45 HST 45 A 02808 Spark Electrode 1 1 B 02837 IgnitionWire 1 1 05795 Orifice NG 05747 Orifice LP D 027...

Page 23: ...08850 F202851 MHT 45LP BurnerBoxfor F208851 B F106250 MHT HST 45 Tube Set C 06014 Hanger D 06016 Hanger Clamp E 06008 9 MHT HST 45 R eflector F 06009 Reflector End Cap MHT HST45Tube Heater REPLACEMENT...

Page 24: ...and address of the dealer from whom you purchased our product The foregoing is the full extent of the responsibility of the Company There are no other warranties express or implied Specifically there...

Reviews: