background image

14

Enerco Group, Inc.,  | Gas-Fired Low-Intensity Infrar ed Heater

Operating Instructions and Owner’s Manual

MINIMUM HEIGHT FROM ROOF

TO LOWEST DISCHARGE OPENING

Roof Pitch

H (Min)

Flat       to 6/12

1.0 Feet

Over  6/12 to 8/12

1.5 Feet

Over  8/12 to 10/12

2.5 Feet

Over 10/12 to 12/12

4.0 Feet

Over 12/12 to 16/12

6.0 Feet

Over 16/12 to 20/12

7.5 Feet

2. All other gas vents shall terminate not less than 2 feet (0.6m)

above the highest point where they pass through the roof and
at least 2 feet (0.6m) higher than any portion of a building
located within 10 feet (3.1m) as shown in the following
illustration.

Venting/Ducting

For Commercial and Industrial Installations Only

General Requirements

Use aluminum or teflon tape suitable for 550°F (3M Company
tapes #433 or #363) or RTV silicone sealant.

Heater must be vented in accordance with specification ANSI

Z223.1 - latest revision

. Partial information relating to this

specification is provided in this section with regard to size and
configurations for venting arrangements. For complete information
consult

ANSI Z223.1 - latest revision

 and applicable local codes.

Use the following guidelines to help insure an adequate, safe
ventin arrangement.

Vent Pipe

 (Single Wall)

Seal joint &
annular space.

2" Clearance

Boot Flashing

Storm Collar

Vent Pipe

Type B

(Double Wall)

Vent Cap

Type B

10ft. or less

 2ft. min.

c) Horizontal Through the Sidewall

This heater, when horizontally vented, must be installed with
the approved venting system.
When venting the heater horizontally through a combustible
outside wall, the same requirements listed previously for Venting

Through the Roof

 apply except as follows:

1. When venting the heater to the outside of the building through

a sidewall, use 3 inch O.D. single-wall metal pipe. This is to be
constructed of galvanized sheet metal or other approved

noncombustible, corrosion-resistant material as indicated by

state and/or local codes.

2. For horizontal venting, the vent lengths may be as follows:

Minimum Equivalent Length = 5 feet of Pipe
Maximum Equivalent Length = 25 feet of Pipe

Use the following correction factors to obtain the equivalent length:

NOTE

: To minimize problems associated with

 condensation in long runs, vent pipe can be

insulated.

3. The horizontal venting system approved with this heater consists

of the Side Wall Vent Kit (02840) shown are page 3.

4. Limit the quantity of 90° elbows to two. When vent pipe is in a

horizontal run, it must be pitched downward ¼ inch per foot
towards the vent terminal. The heater must be installed level.

5. The horizontal venting system shall not terminate:

a) Less than 4 feet (1.2m) below, 4 feet (1.2m) horizontally from,
or 1 foot (30cm) above any door, window or gravity air inlet into
any building. The bottom of the vent terminal shall be located at
least 7 feet (2.1m) above grade or above snow accumulation
levels as determined by local codes.

b) Less than 3 feet (0.9m) from a combustion air inlet.

c) Less than 3 feet (0.9m) from any other building opening or
any gas service regulator.

d) Directly over areas where condensate or vapor could create a
nuisance or hazard or be harmful to the operation of gas utility
meters, regulators, relief valves, or other equipment. Building
materials should be protected from flue gases and condensate.

6. In regions of the country where prevailing winds are consistently

higher than 40 mph, it may be necessary to terminate the vent
system above the roof level.

Single-Wall
Vent Pipe

Wall Thimble

Wall

18"

Vent Cap

Type “B” Vent

a) Subtract 15 feet if the run is horizontal

b) Subtract 10 feet for an approved vent cap.
c) Subtract 10 feet for each elbow beyond 15 feet from the heater.

d) Subtract 15 feet for each elbow within 15 feet of the heater.

  for an approved vent cap you have ---------10 ft.

  for a horizontal run you have -----------------15 ft.

Your Maximum Equivalent Length is ---------------- 25 ft.

EXAMPLE

Summary of Contents for HEATSTAR HST 45

Page 1: ...service must be performed by a qualified installer service agency or the gas supplier If you cannot reach your gas supplier call the Fire Department Gas Fired Low Intensity Infrared Heaters approved f...

Page 2: ...e conformer aux precautions et aux instructions a fourni avec cet appareil de chauffage avoir pour resultat la mort blessure et la perte de propriete ou les dommages physiques serieuses du danger de f...

Page 3: ...er of body oils from the hands to the surface of the reflector VentKit F102840 1 2 3 x 2 Pipe 26GA 2 1 36 x 3 B Vent 3 1 Gas Vent Top 3 4 1 Adj Wall Thimble 5 1 Storm Collar 6 1 3 Elbow 7 1 Adj Roof F...

Page 4: ...iant energy downward to the space to be heated Heat Exchanger A U shaped tube through which the heated products of combustion pass Rear Movable Hanger Provides support for the heat exchanger and refle...

Page 5: ...Hz single phase 1 amp Connection 3pinmoldedplug Gas Inlet Connection Connection Male NPT Gas Inlet Pressure The minimum inlet gas supply pressure for the purpose of input adjustment Natural Gas Minimu...

Page 6: ...HSTtube heater Specifiesthenationalstandardsandapplicablecodes that apply to the gas electric and venting requirements Specifies the national standards and applicable codes that apply to non resident...

Page 7: ...the floor Minimum required safe distances to combustibles must be maintained from vehicles parked below the heater When installed over hoists the minimum required safe distances to combustible must b...

Page 8: ...ose Location for Heater When selecting a suitable mounting location for the MHT HSTtube heater it is important to consider the following 1 The heater must meet the minimum mounting height requirement...

Page 9: ...s when stored under this heater will be subjected to radiant heat and could be seriously damaged 4 All horizontal venting sections must slope away from the heater at a rate of per foot 5 The total len...

Page 10: ...d through the roof be sure to carefully review the roof option installa tion portion of this section Ensure that the selected mounting site will satisfy the measurement param eters vent length not to...

Page 11: ...e tube ends extend through the flanges to help with alignment 3 Using the four long and four short nuts from the bolt kit 02876 secure the tube set to the burner box As shown in the diagram use the fo...

Page 12: ...current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved d...

Page 13: ...re consistently higher than 40 mph it may be necessary to terminate the vent system above the roof level Other venting references can be found in equipment volume of the ASHRAE Handbook A SINGLE HEATE...

Page 14: ...approved noncombustible corrosion resistant material as indicated by state and or local codes 2 For horizontal venting the vent lengths may be as follows Minimum Equivalent Length 5 feet of Pipe Maxi...

Page 15: ...problem the flue length should be shortened or insulated g For vent specifications all of the following conditions must be met The maximum equivalent length of vent pipe should be carefully observed A...

Page 16: ...Adequate clearances around the perforated fresh air plate must be maintained at all times In larger open areas of buildings infiltration normally is adequate to provide air for combustion DirectOutsid...

Page 17: ...Use wrought iron or wrought steel pipe and malleable iron fittings The use of copper tube and brass fittings is acceptable WARNING Electrical Shock Hazard Plugheaterinto groundedthreeprongceilingrecep...

Page 18: ...Use LP resistant joint compound on all threads 4 Check the pipe and tube connections for leaks before placing heating equipment into service When checking for gas leaks use a soap and water solution...

Page 19: ...ur 8 Periodic visual check of burner flame while unit is in operation through sight glass in bottom of unit Section 6 MAINTENANCE Pre Season Maintenance Heater area to be kept clear and free form comb...

Page 20: ...iter spark gap incorrect Try This Unplug heater power cord from the electrical outlet wait for a minimum of five seconds Plug heater cord back into outlet Unplug heater power cord from the electrical...

Page 21: ...equirements contact the gas company Check for 24V across valve terminals Check Shutoff On Valve IF NO Check wiring between the ignition module and the valve Repair replace wires as required If wiring...

Page 22: ...rs on the illustrations are keyed to the associated parts list E ITEM PART NUMBER DESCRIPTION MHT 45 HST 45 A 02808 Spark Electrode 1 1 B 02837 IgnitionWire 1 1 05795 Orifice NG 05747 Orifice LP D 027...

Page 23: ...08850 F202851 MHT 45LP BurnerBoxfor F208851 B F106250 MHT HST 45 Tube Set C 06014 Hanger D 06016 Hanger Clamp E 06008 9 MHT HST 45 R eflector F 06009 Reflector End Cap MHT HST45Tube Heater REPLACEMENT...

Page 24: ...and address of the dealer from whom you purchased our product The foregoing is the full extent of the responsibility of the Company There are no other warranties express or implied Specifically there...

Reviews: