18677 Rev. A 8/05
FIGURE 15:
Common Roof Venting
COMMON VENTING - (2) Heaters
Model#
H = 6 ft.
H = 8 ft.
H = 15ft.
ERXL-60
D = 7”
D = 6”
D = 6”
ERXL-80
D = 8”
D = 7”
D = 6”
ERXL-100
D = 8”
D = 8”
D = 7”
ERXL-125
D = 10”
D = 10”
D = 8”
ERXL-150
D = 10”
D = 10”
D = 8”
ERXL-175
D = 10”
D = 10”
D = 8”
COMMON VENTING - (4) Heaters
Model#
H = 6 ft.
H = 8 ft.
H = 15ft.
ERXL-60
D = 10”
D = 10”
D = 8”
ERXL-80
D = 10”
D = 10”
D = 10”
ERXL-100
N/A
D = 12”
D = 10”
ERXL-125
N/A
D = 12”
D = 10”
ERXL-150
N/A
N/A
D = 12”
ERXL-175
N/A
N/A
D = 12”