Levelflex FMP53 HART
Electrical connection
Hauser
31
4-wire, 4-20mA HART, active
"Power supply; Output"
Terminal voltage
Maximum load R
max
K:
4-wire 90-253VAC; 4-20mA HART
90 to 253 V
AC
(50 to 60 Hz), overvoltage category II
500 Ω
L:
4-wire 10,4-48VDC; 4-20mA HART
10.4 to 48 V
DC
1)
Feature 020 of the product structure
7.1.4
Overvoltage protection
If the measuring device is used for level measurement in flammable liquids which requires the
use of overvoltage protection according to DIN EN 60079-14, standard for
test procedures 60060-1 (10 kA, pulse 8/20 μs), an overvoltage protection module has to be
installed.
Integrated overvoltage protection module
An integrated overvoltage protection module is available for 2-wire HART as well as
PROFIBUS PA and FOUNDATION Fieldbus devices.
Product structure: Feature 610 "Accessory mounted", option NA "Overvoltage protection".
Technical data
Resistance per channel
2 × 0.5 Ω max.
Threshold DC voltage
400 to 700 V
Threshold impulse voltage
< 800 V
Capacitance at 1 MHz
< 1.5 pF
Nominal arrest impulse voltage (8/20 μs)
10 kA
External overvoltage protection module
HAW562 or HAW569 from Hauser are suited as external overvoltage protection.
For detailed information please refer to the following documents:
• HAW562: TI01012K
• HAW569: TI01013K
7.2
Connecting the measuring device
L
WARNING
Risk of explosion!
‣
Observe applicable national standards.
‣
Comply with the specifications in the Safety Instructions (XA).
‣
Use specified cable glands only.
‣
Check to ensure that the power supply matches the information on the nameplate.
‣
Switch off the power supply before connecting the device.
‣
Connect the potential matching line to the outer ground terminal before applying the
power supply.