Electrical connection
Levelflex FMP53 HART
28
Hauser
7.1.3
Power supply
2-wire, 4-20mA HART, passive
2-wire; 4-20mA HART
"Approval"
Terminal voltage U at
the device
Maximum load R, depending on the supply voltage U
0
at the supply
unit
• Non-Ex
• Ex nA
• Ex ic
• CSA GP
11.5 to 35 V
U0 [V]
10
11.5
22.5
20
30
35
0
500
R [ ]
W
A0035511
Ex ia / IS
11.5 to 30 V
• Ex d / XP
• Ex ic[ia]
• Ex tD / DIP
13.5 to 30 V
R [ ]
Ω
[V]
U0
10
13.5
24.5
20
30
0
500
A0034969
1)
Feature 020 of the product structure: option A
2)
Feature 010 of the product structure
3)
For ambient temperatures T
a
≤ -30 °C (-22 °F) a minimum voltage of 14 V is required for the sartup of the device
at the MIN error current (3,6 mA). For ambient temperatures T
a
≥ 60 °C (140 °F) a minimum voltage of 12V is
required for the sartup of the device at the MIN error current (3,6 mA). The startup current can be parametrized.
If the device is operated with a fixed current I ≥ 4,5 mA (HART multidrop mode), a voltage of U ≥ 11,5 V is
sufficient throughout the entire range of ambient temperatures.
4)
For ambient temperatures T
a
≤ -20 °C (-4 °F) a minimum voltage of 16 V is required for the startup of the device
at the MIN error current (3.6 mA).