74
Technical data
The information given in the table applies to the following operating conditions
(standard reference conditions):
standard reference
conditions
The usable power output can deviate from the nominal values depending on the
actual operating conditions. The following table provides guide points:
Power reduction
The following table shows you the applicable Operating conditions for running
the generator:
ambient conditions
Name
Value
Unit
Set-up height above sea level
100
[m]
Ambient temperature
25
[°C]
Relative Air humidity
30
[%]
Reference value
Power output
reduction
for each ad-
ditional
Set-up height above sea level
1 %
100 m
Ambient temperature
4 %
10°C
Name
Value
Unit
Set-up height above sea level
max. 2,000
[m]
Ambient temperature
-20 to +40
[°C]
Relative air humidity
max. 95, non-
condensing
[%]
Tilt angle
max. 20
[°]