Operation
TTR31, TTR35
20
Hauser
Output 1
.
Output 2,
as option
.
Switch-back point
value
,M,
Switch-back point
-50 to 149 °C
(-58 to 300 °F)
in increments of 0.1 °C
(0.18 °F)
.
Switch point delay
,M,
Delay time
0...99 s
in increments of 0.1 s
Factory setting:
0 s
.
Switch-back point
delay
,M,
Delay time 0...99 s
in increments of 0.1 s
Factory setting:
0 s
Min. distance between SP and RSP: 0.5 °C/K (0.9 °F)
0>.,
Analog
output
Value for 4 mA
(LRV)
,M,
-50 to 130 °C
(-58 to 266 °F)
Lower range value in
increments of 0.1 °C
(0.18 °F)
Factory setting:
0.0 °C (32.0 °F)
Value for 20 mA
(URV)
,M,
-30 to 150 °C
(-22 to 302 °F)
Enter upper range value
in increments of 0.1 °C
(0.18 °F)
Factory setting:
150 °C (302 °F)
7 @
Temperature
applied for 4 mA
(LRV)
,M,
Take temperature value
as lower range value
(not via PC software)
7 @
Temperature
applied for 20 mA
(URV)
,M,
Take temperature value
as upper range value
(not vial PC software)
Function
group
Function
Settings
Description