TTR31, TTR35
Installation
Hauser
9
"
Caution!
The maximum process pressure for the conical metal-metal process connection
(
Fig. 4, item MB) is 16 bar = 1.6 MPa (232 psi)!
3.4 Installation
instructions
"
Caution!
Do no thread into process connection by turning housing. Always use a wrench (see table,
Chap. 3.3) on the process connection flats (
Fig. 5, Pos. 1) to tighten the sensor into the
process connection.
A0011644
Fig. 5: Possible installation options for temperature monitoring in pipes
m
TTR31
n
TTR35 for use in hygienic processes
General mounting instructions:
• Installation at angle pieces, against the direction of flow (
• Installation in smaller pipes, inclined against the direction of flow (
Fig. 5, Item B).
• Installation vertical to the direction of flow (
Fig. 5, Item C). Installation of TTR35 by min.
3° inclination, because of self draining.
• The on-site display can be rotated electronically 180°
−
see section 5.1 "On-site operation".
• The housing can be rotated up to 310°.