BA229R/09/en/06.09
71098142
Release 01.02

Operating manual

Thermophant

®

 T TTR31, TTR35

Temperature switch

Summary of Contents for Thermophant T TTR 35

Page 1: ...BA229R 09 en 06 09 71098142 Release 01 02 Operating manual Thermophant T TTR31 TTR35 Temperature switch ...

Page 2: ...s you can commission your system easily and swiftly Safety instructions Page 4 Æ Installation Page 6 Æ Wiring Page 11 Æ Operation Page 12 Display and operating elements On site operation Operation with PC and configuration software Æ Trouble shooting Page 28 ...

Page 3: ...tions 9 4 Wiring 11 4 1 DC voltage version with M12x1 connector 11 4 2 DC voltage version with valve connector 12 5 Operation 12 5 1 On site operation 12 5 2 Operation with PC 22 6 Maintenance 24 7 Accessories 25 7 1 Welding bosses and coupling 25 7 2 Electrical connection 26 7 3 Configuration kit 27 7 4 Configuration software 27 8 Trouble shooting 28 8 1 Errors and warnings 28 8 2 Repair 29 8 3 D...

Page 4: ...The measuring device meets the general safety requirements according to EN 61010 1 and the EMC requirements according to IEC EN 61326 in addition to the NAMUR recommendations NE 21 NE 43 and NE 53 Functional safety The Thermophant T temperature switches were developed according to the standards IEC 61508 and IEC 61511 1 FDIS The device version with PNP switch output and additional analog output is...

Page 5: ...om the point of view of safety It complies with the standards EN 61010 1 Protection Measures for Electrical Equipment for Measurement Control Regulation and Laboratory Procedures and with the EMC requirements of IEC EN 61326 The device meets the legal requirements of the EU Directives The manufacturer confirms a positive completion of all tests by fitting the unit with a CE mark Hygiene standard T...

Page 6: ...ge Check that the goods delivered are complete and nothing is missing Storage Storage temperature 40 C to 85 C 40 F to 185 F 3 2 Dimensions T09 TTR31xxx 06 xx xx en 000 Fig 2 Dimensions in mm inches L Insertion length M12x1 connector as per IEC 60947 5 2 M16x1 5 or NPT valve plug as per DIN 43650A ISO 4400 ø 42 3 1 66 97 1 3 82 42 1 1 66 38 7 1 52 36 1 42 24 0 95 52 2 05 ø 38 5 1 52 L L ø ø 6 0 24...

Page 7: ...on Insertion length L Thread length L1 Thread length L2 A Without process connection For suitable welding boss and coupling see chapter accessories 50 100 or 200 mm 1 97 3 94 or 7 87 in B Thread process connection ANSI NPT m AF14 ANSI NPT m AF27 14 3 mm 0 56 19 mm 0 75 5 8 mm 0 23 8 1 mm 0 32 C Thread process connection cylindrical as per ISO 228 G n AF14 G n AF27 12 mm 0 47 14 mm 0 55 ...

Page 8: ...l metal for hygienic processes G thread thread length L1 14 mm 0 55 Suitable welding boss available as accessory DB Clamp 1 1 ISO 2852 or DN 25 DN 40 DIN 32676 DL Clamp 2 ISO 2852 or DN 50 DIN 32676 DP Clamp 2 ISO 2852 LB Varivent F DN25 32 PN 40 LL Varivent N DN40 162 PN 40 HL APV Inline DN50 PN40 316L B bores 6 x Ø8 6 0 34 2 x thread M8 PL DIN 11851 DN50 PN40 including coupling nut PG DIN 11851 ...

Page 9: ...cess connection A0011644 Fig 5 Possible installation options for temperature monitoring in pipes m TTR31 n TTR35 for use in hygienic processes General mounting instructions Installation at angle pieces against the direction of flow Fig 5 Item A Installation in smaller pipes inclined against the direction of flow Fig 5 Item B Installation vertical to the direction of flow Fig 5 Item C Installation ...

Page 10: ...n hygienic processes a0011673 en Fig 6 Installation in hygienic processes A Milk pipe connection as per DIN 11851 connection PL PG PH only in linkage with EHEDG certified and self centering ring B Varivent and APV Inline connection LB LL HL C Clamp as per ISO 2852 connection DB DL DP ...

Page 11: ...d m R2 A2 2x PNP switch outputs R1 and m diagnosis break contact with adjustment DESINA A3 1x PNP switch output and 1x analog output 4 to 20 mA A4 1x analog output 4 to 20 mA and 1x PNP switch output m R2 A4 1x analog output 4 to 20 mA and 1x PNP switch output m diagnosis break contact with adjustment DESINA Caution To avoid the analog input damaging of a PLC do not connect the active PNP switch o...

Page 12: ... with M 16x1 5 or NPT valve plug B 1x PNP switch output 5 Operation 5 1 On site operation The Thermophant T is operated by means of three keys The digital display and the light emitting diodes LED support navigation in the operating menu T09 TTR31xxx 19 xx xx en 001 Fig 9 Position of operating elements and possibilities for display ...

Page 13: ...r change parameters with the or key Then return to Function with the E key Note If software locking is enabled it must be disabled before making entries or changes q Press the E key several times to return to the Function group until the appropriate function group is reached again r Jump back to the measuring position Home position Press the E key for longer than 3 s s Query to save data select YE...

Page 14: ...Operation TTR31 TTR35 14 Endress Hauser 5 1 2 Structure of the operating menu for 1x or 2x switch outputs A0008102 Fig 11 Operating menu A function groups B functions C settings ...

Page 15: ...r 1x analog output 4 to 20 mA At devices with analog output both output 1 and output 2 can be configured as an analog output Furthermore it is possible to configure both output 1 and output 2 as a switch output T09 TTR31xxx 19 xx xx xx 003 Fig 12 Operating menu A function groups B functions C settings ...

Page 16: ...ion adjustment within 10 C K 18 F of the upper range limit 7 Accept zero point M No settings possible not available in PC software Display 66 66 PV measured value display PVRO measured value display rotated 180 SP set switch point display SPRO set switch point display rotated 180 OFF display off OFFR display off rotated 180 Factory setting measured value PV Damping display value output signal M Me...

Page 17: ...ct This switch function is freely selectable Factory setting if no customer specific settings have been ordered Switch point SP 1 45 C 113 0 F Switch back point RSP 1 44 5 C 112 1 F Switch point SP 2 55 C 131 0 F Switch back point RSP 2 54 5 C 130 1 F Range of adjustment LRL Lower Range Limit URL Upper Range Limit LRV Lower Range Value URV Upper Range Value DESINA PIN assignment of the M12 connect...

Page 18: ...ow NO contact p Hysteresis NO contact SP switch point RSP switch back point Function group Function Settings Description Output 1 Output 2 as option 6 6 Switching characteristic WINC window NC contact HYNC hysteresis NC contact WINO window NO contact HYNO hysteresis NO contact Factory setting HYNO Switch point value M Switch point 49 5 to 150 C 57 1 to 302 F in increments of 0 1 C 0 18 F ...

Page 19: ...g 0 s Switch back point delay M Delay time 0 99 s in increments of 0 1 s Factory setting 0 s Min distance between SP and RSP 0 5 C K 0 9 F Function group Function Settings Description Output 1 Output 2 as option 6 6 Switching characteristic 0 WINC window NC contact HYNC hysteresis NC contact WINO window NO contact HYNO hysteresis NO contact 4 20 analog output Factory setting HYNO Switch point valu...

Page 20: ... between SP and RSP 0 5 C K 0 9 F 0 Analog output Value for 4 mA LRV M 50 to 130 C 58 to 266 F Lower range value in increments of 0 1 C 0 18 F Factory setting 0 0 C 32 0 F Value for 20 mA URV M 30 to 150 C 22 to 302 F Enter upper range value in increments of 0 1 C 0 18 F Factory setting 150 C 302 F 7 Temperature applied for 4 mA LRV M Take temperature value as lower range value not via PC software...

Page 21: ...ance between SETL and SETU 20 C K 36 F Function group Function Settings Description Function group Function Settings Description Service functions Locking code Enter the locking code for enabling the device Change locking code Freely selectable code 1 9999 0 no locking A locking code already assigned can only be changed by first entering the old code for enabling the device Reset Reset all entries...

Page 22: ... configuration software ReadWin 2000 or FieldCare Item 2 Configuration kit TXU10 AA or FXA291 Item 3 Temperature switch Service functions if output 2 available Simulation output 1 or 2 66 M1 if analog output available OFF No simulation OPEN Switch output open CLOS Switch output closed 3 5 Simulation values for analog output in mA 3 5 4 0 8 0 12 0 16 0 20 0 21 7 Max indicator M Display of max measu...

Page 23: ...n 5 2 3 Hints for the configuration with FieldCare FieldCare is an universal configuration software based on FDT DTM technology Note To configure the Thermophant T TTR31 35 with FieldCare the PCP ReadWin Communication DTM and the Thermophant Device DTM are required All devices with software version 1 01 00 or higher can be configured with FieldCare Function group Description SERV Number of switch ...

Page 24: ... manual BA027S c4 or see www endress com 6 Maintenance Any buildup on the sensor can have a negative effect on the sensor response time For this rea son check the sensor for buildup at regular intervals Caution Make sure the process is unpressurized before you remove the device Do not twist the device out of the process connection thread at the housing Always use a suitable open ended wrench for d...

Page 25: ...lding boss with sealing taper metal metal Collar welding boss moveable with sealing taper and pressure screw material of parts in contact with the process 316L PEEK max process pressure 10 bar 145 psi Order number 51004751 T09 TSM470AX 06 09 00 en 000 Material of parts in contact with process 316L Order no 51004752 T09 TSM470BX 06 09 00 en 000 Welding boss Seal metal metal Material of parts in con...

Page 26: ... connecting cable straight connection to M12x1 housing connector Order number 52006263 P01 PMP13xxx 00 xx 00 xx 003 Coupling M12x1 for simple user installable assembly of the connecting cable elbowed connection to M12x1 housing connector IP 67 PG7 Order number 51006327 T09 TTR3xxxx 06 09 xx en 000 PVC cable preassembled 4 x 0 34 mm2 22 AWG with M12x1 coupling elbowed screw plug length 5 m 16 4 ft ...

Page 27: ...m 16 4 ft specially for hygiene applications IP 69K Order number 52018763 Display gn device operational ye1 switch status 1 ye2 switch status 2 Note Not for use at devices with 4 to 20 mA analog output option T09 TTR31xxx 00 00 xx xx 001 ye 1 ye 2 gn Configuration kit for PC programmable transmitters ReadWin 2000 setup program and interface cable for PCs with USB port and 4 pole post connector Ord...

Page 28: ...cification Check medium temperature return device to E H where necessary E019 Power supply outside specification Check operating voltage E015 Memory error Return device to E H E020 E021 E022 Power is only supplied to the device via the communication interface measurement is deactivated Check operating voltage E025 Switching contact 1 is not open although it should be Switching contact defective re...

Page 29: ...simulation for output 1 and output 2 W202 Measured value outside of the sensor range Operate the device in the specified temperature range W209 Device starts W210 Configuration modified warning code will be displayed for 15 s approx W212 Sensor signal outside the permitted range Operate the device in the specified temperature range W250 Number of switch cycles exceeded Replace the device W270 Shor...

Page 30: ...ity and operation Compatibility provided Operating Instructions change ZZ Trouble shooting and internal modifications Operating Instructions do not change Date Release no device Changes in software Documentation 06 2004 01 00 00 KA174r 09 en 51008032 12 2004 01 01 00 New analog electronics BA201r 09 en 02 05 51009833 02 2005 01 02 00 Internal BA201r 09 en 02 05 51009833 02 2006 01 02 01 Parameter ...

Page 31: ...us as if not supplied with power switch open 9 2 Output Switching capacity Switch status ON Ia 250 mA Switch status OFF Ia 1 mA Switching cycles 10 000 000 Voltage drop PNP 2 V Overload protection Automatic load testing of switching current output is switched off in case of overcurrent the switching current is tested again every 0 5 s max capacitance load 14 μF for max supply voltage without resis...

Page 32: ...mm 0 79 with process connection Process pressure limits Maximum permitted process pressure depending on the insertion length a0008063 en Fig 15 Maximum permitted process pressure L insertion length p process pressure The diagram takes into consideration not only the overpressure but also the pressure load caused by the flow whereby a safety factor of 1 9 has been specified for operation with flow ...

Page 33: ...cess connection see Fig 4 item MB is 16 bar 1 6 MPa 232 psi Permitted flow velocity depending on the insertion length a0008065 en Fig 16 Permitted flow velocity L insertion length during flow v flow velocity Medium air water The permitted flow velocity is the minimum from resonance velocity resonance distance 80 and load or buckling caused by flow which would lead to failure of the thermometer tub...

Page 34: ...Dangerous good sheet TTR31 TTR35 34 Endress Hauser 10 Dangerous good sheet ...

Page 35: ...TTR31 TTR35 Dangerous good sheet Endress Hauser 35 ...

Page 36: ...BA229R 09 en 06 09 71098142 FM9 0 ...