Teqwave H
Commissioning
Hauser
47
Parameter overview with brief description
Parameters
Procedure
Selection/input
Factory setting
Measuring range Max
Enter the upper limit for the
selected measured variable or
20 mA current/10 V voltage, while
paying attention to the measuring
range limits → 80 and the
concentration app data sheet.
Positive decimal
• Analysis parameter 1…n:
depends on the selected
concentration app
• Temperature: 120.0
• Speed of sound: 2000.00
• Density: 1500.00
Measuring range Min
Enter the lower limit for the
selected measured variable or
4 mAcurrent/0 V V voltage, while
paying attention to the measuring
range limits → 80 and the
concentration app data sheet.
Positive decimal
• Analysis parameter 1…n:
depends on the selected
concentration app
• Temperature: 0.0
• Speed of sound: 600.00
• Density: 700.00
Decimal places
Select the number of decimal places
for the value of the measuring
range.
• 0
• 1
• 1 ±0.5
• 2
• 2 ±0.5
• 3
• 3 ±0.5
• 4
• Analysis parameter 1…n: 2
• Temperature: 1
• Speed of sound: 2
• Density: 1 ±0.5
10.4.6 Configuring the relay output
The
Relay output
menu contains all the parameters for configuring the relay output.
Navigation using transmitter with touch screen
1. Settings menu → "Application parameters" → "Relay output" → "Settings" → "Select
measured value" → "Output mode"
2. Settings menu → "Application parameters" → "Relay output" → "Settings" → "Select
measured value" → "Switch point Max"/"Switch point Min" or "Switch point"
3. Settings menu → "Application parameters" → "Relay output" → "Settings" → "Hysteresis"
4. Settings menu → "Application parameters" → "Relay output" → "Settings" → "NC
contact/NO contact"
5. Settings menu → "Application parameters" → "Relay output" → "Output"
Navigation using the Viewer
1. Menu "Teqwave Transmitter" → "Relay output" → Select measured variable" → "Output
mode"
2. Menu "Teqwave Transmitter" → "Relay output" → Select measured variable → "Switch
point Max"/"Switch point Min" or "Switch point"
3. Menu "Teqwave Transmitter" → "Relay output" → "Select measured variable" →
"Hysteresis"
4. Menu "Teqwave Transmitter" → "Relay output" → Select measured variable" → "NC
contact/NO contact"
5. Menu "Teqwave Transmitter" → "Relay output" → "Output"
The operating tool communicates the settings to the transmitter as soon as the
Apply
button is clicked.