Overfill Prevention System SOP600
10
Hauser
requirements of the EC Directive. Hauser confirms the conformity of the devices by affixing
to them the CE mark.
Ex approval
The cabinet, the text display unit and the outside signaling unit must be mounted in a non-
hazardous area. The Liquiphants can be mounted in hazardous areas. Information about currently
available hazardous area versions (IECEx, ATEX Ex ia; TIIS; NEPSI; FM ist; CSA IS) depend on the
Liquiphants used.
WHG overfill prevention
• Overfill detection system: Z-65-11-507
• Leak detection system: Z-65-40-508
Functional safety
For safety functions in conjunction with FEL85 to SIL3 (MAX detection), see the
Functional Safety
Manual (SIL) SD00350F/00/EN
.
For safety functions in conjunction with FEL57 to SIL2 (MAX detection), see the
Functional Safety
Manual (SIL) SD00111F/00/EN
Other standards and
guidelines
• EC Low Voltage Directive 2014/35/EU
• IEC/EN 60204-1
Safety of Machinery - Electrical Equipment of Machines
• IEC 61508
Functional Safety of Electrical/Electronic/Programmable Electronic Safety-related Systems (E/E/
PES)
• IEC 61511:2003
Functional safety
Safety Instrumented Systems for the Process Industry Sector, 2003
Ordering Information
Order code:
SOP600 -
010
020
030
040
050
060
070
080
090
510
570
610
Feature
Description
Option model
010
System
A
Automated Overfill Prevention System
(AOPS)
M
Manual Overfill Prevention System (MOPS)
020
Safety Integrity Level
2
2 (only High-High level SIL certified)
3
3 (only High-High level SIL certified)
9
Special version, TSP-no. to be spec.
030
Max. number of tanks
A11
4 (High-High level), AOPS
A12
8 (High-High level), AOPS
A13
12 (High-High level), AOPS
A14
16 (High-High level), AOPS
A21
4 (High + High-High level), AOPS
A22
8 (High + High-High level), AOPS
A23
12 (High + High-High level), AOPS
A24
16 (High + High-High level), AOPS
M11
4 (High-High level), MOPS
M12
8 (High-High level), MOPS
M13
12 (High-High level), MOPS
M14
16 (High-High level), MOPS