Commissioning
Smartec S CLD132/134 PROFIBUS-PA/-DP
30
Hauser
6
Commissioning
6.1
Function check
WARNING
!
Incorrect connection, incorrect supply voltage
Safety risks for staff and incorrect operation of the device
‣
Check that all connections have been established correctly in accordance with the wiring
diagram.
‣
Make sure that the supply voltage matches the voltage indicated on the nameplate.
6.2
Setting of device address
The address must be set for each PROFIBUS device. The process control system does not
recognize the transmitter if the address is not set correctly.
All devices have the address 126 on leaving the factory. You can use this address for device
function checking and for connection to a PROFIBUS PA network. You must change this
address to be able to integrate additional devices.
The device address can be set via:
• Local operation
• PROFIBUS communication
• DIL switch in the device
Valid device addresses are in the range 0 to 125.
Each address may only be given once in a PROFIBUS network.
The double arrow in the display indicates active communication with PROFIBUS.
Position of the DIL switch
a0005929
Fig. 12:
Position of the DIL switch (only accessible with open housing cover)
You can only set the address via the
software if DIL switch 8 is set to "ON". The
factory setting of the DIL switch is "ON"
(
a0005211
Fig. 13:
Factory setting of the DIL switch