RN42
Mounting
Hauser
9
4.5
Storage and transport
When storing and transporting the device, pack it so that it is reliably protected
against impact. The original packaging provides optimum protection.
5
Mounting
5.1
Mounting requirements
5.1.1
Dimensions
The dimensions of the device are provided in the 'Technical data' section of the Operating
Instructions.
5.1.2
Mounting location
The device is designed for installation on 35 mm (1.38 in) DIN rails in accordance with IEC
60715 (TH35).
NOTICE
‣
When using in hazardous areas, the limit values of the certificates and approvals must
be observed.
For information on ambient conditions, see the "Technical data" section.
5.2
Installing a DIN rail device
The device can be installed in any position (horizontal or vertical) on the DIN rail without
lateral clearance from neighboring devices. No tools are required for installation. The use
of end brackets (type "WEW 35/1" or equivalent) on the DIN rail is recommended to fix the
device.
If several devices are installed side by side, it is important to ensure that the
maximum side wall temperature of the individual devices of 80 °C (176 °F) is not
exceeded. If this cannot be guaranteed, mount the devices at a distance from one
another or ensure sufficient cooling.
1.
2.
3.
A0041736
2
Installing on DIN rail
1. Position the top DIN rail groove at the top end of the DIN rail.