Mounting FMU 130, 131, 230, 231
With Counter Nut or Welded Sleeve
Thread Versions:
• Prosonic T FMU 130, 230 with G 1½ or 1½ NPT
• Prosonic T FMU 131, 231 with G 2 or 2 NPT
Mounting on a Nozzle
If the maximum level to be measured falls within the blocking distance, the transmitter
must be mounted on a nozzle. Please note that if product enters the blocking distance,
the device will not measure correctly.
• No buildup should form in the nozzle.
• The recommend nozzle dimensions are limits, within which the nozzle can vary. Select
as big a nozzle diameter as possible
, but keep
the height as small as possible
• The inner surface of the nozzle should be as smooth as possible (no edges or welding
seams).
• Interference echoes caused by the nozzle can be suppressed by the echo suppression
function when a display is used for operation (see page 25).
Nozzle: Height and Diameter
Sensor FMU D
min
In. (mm)
L
max
In. (mm)
130 / 230
1.96 (50)
5.90 (150)
130 / 230
3.14 (80)
9.44 (240)
130 / 230
3.93 (100)
15.0 (380)
131 / 231
3.14 (80)
9.44 (240)
131 / 231
3.93 (100)
15.0 (380)
232
3.93 (100)
11.8 (300)
Mounting on a Nozzle
Operation without Display
FMU 130, 131, 230, 231, 232
D
min
=3.93 in. (100 mm)
L
max
=5.90 in. (150 mm)
Operation with Display or Commuwin II
Please use the possibilities of echo
suppression (see page 25)
deburr edges
Standard Mounting
Mounting with Counter Nut
counter nut
welded sleeve
welded sleeve
Mounting with Welded Sleeve