29
Hauser
Prosonic T - FMU 130, 131, 230, 231, 232
Fault Analysis
Current Output
Possible Cause
Removal
➀
Bar display flashes.
Response of the current
output
Error code in V9H0.
– Which error code?
depends on the
setting in V0H7.
See page 28.
– Further action depends on the error
V0H7 = 0
-10%
2.4 mA or
code.
3.8 mA
V0H7 = 1
110%
22 mA
E641 in V9H0
– Check sensor position.
V0H7 = 2
HOLD
Last value
Echo too weak or
See pages 8-11, 25.
is held
foam on the surface.
➁
Measured value in
Distance D in V0H8
Multiple echo?
See
➄
V0H0 too small.
too large?
– Gas layering? Contact E+H Service.
– Check sensor position.
See pages 8-11, 25.
Incorrect linearization?
– Re-enter linearization curve
See pages 22 – 23.
Incorrect current output?
– Check values in V0H5 and V0H6
and re-enter if necessary.
See page 24.
➂
Measured value in
Distance D in V0H8
Interference from internals in the
V0H0 too large.
too small?
measuring range?
Instrument mounted in nozzle?
– Check dimensions of nozzle.
See page 9.
– Check sensor position.
See pages 8-11, 25.
– Select application parameter
0 or 2 in V0H3.
See page 21.
– Carry out interference echo
suppression.
See page 25.
Incorrect linearization?
Re-enter linearization curve.
See pages 22-23.
Incorrect current output?
Check values in V0H5 and V0H6 and
re-enter if necessary.
See page 24.
yes
yes
yes
yes
yes
yes
yes
no
no
no
no
yes
Expected
Actual
Expected
Actual