Commissioning
Prosonic S FMU90 PROFIBUS DP
74
Hauser
•
AI 8
• Bytes 35 - 38: Overflow totalizer 1 (IEEE754)
• Byte 39: Status totalizer 1
•
AI 9
• Bytes 40 - 43: Value totalizer 2 (IEEE754)
• Byte 44: Status totalizer 2
•
AI 10
• Bytes 45 - 48: Overflow totalizer 2 (IEEE754)
• Byte 49: Status totalizer 2
"Level+Flow" operating mode
•
AI 1
• Bytes 0 - 3: Flow 1 (IEEE754); unit: m
• Byte 4: Status flow 1
•
AI 2
• Bytes 5 - 8: Flow 2 (IEEE754); unit: m
• Byte 9: Status flow 2
•
AI 3
• Bytes 10 - 13: Level 1 (IEEE754); unit: m
• Byte 14: Status level 1
•
AI 4
• Bytes 15 - 18: Level 2 (IEEE754); unit: m
• Byte 19: Status level 2
•
AI 5
• Bytes 20 - 23: Temperature 1 (IEEE754); unit: °C
• Byte 24: Status temperature 1
•
AI 6
• Bytes 25 - 28: Temperature 2 (IEEE754); unit: °C
• Byte 29: Status temperature 2
•
AI 7
• Bytes 30 - 33: Value totalizer 1 (IEEE754)
• Byte 34: Status totalizer 1
•
AI 8
• Bytes 35 - 38: Overflow totalizer 1 (IEEE754)
• Byte 39: Status totalizer 1
•
AI 9
• Bytes 40 - 43: Value totalizer 2 (IEEE754)
• Byte 44: Status totalizer 2
•
AI 10
• Bytes 45 - 48: Overflow totalizer 2 (IEEE754)
• Byte 49: Status totalizer 2
Changing the assigned measured variables
Parameter: Output/calculat. → Analog input → Analog input N → Measured value N
9.5
Simulation
9.5.1
Flow simulation
Navigation
• For flow sensor:
Flow → Flow → Flow N → Simulation
• For upstream sensor in event of backwater or dirt detection:
Flow → Flow 1 + backwater → Flow → Flow 1 → Simulation
• For downstream sensor in event of backwater or dirt detection:
Flow → Flow 1 + Backwater → Backwater → Simulation