Prosonic S FDU90/91/91F/92/93/95/96
6
Hauser
Operating frequency
Output
Signal transmission
analogue voltages
Power supply
Power supply
supplied by the transmitter FMU90
Sensor heater (for FDU91)
The FDU90 and FDU91 sensors are optional available in a version with heater. The power for this heater must
be provided by an external power supply unit. The supply voltage is connected to the brown (BN) and blue
(BU) strands of the sensor cable.
Technical data
• 24 VDC ±10 %; residual ripple < 100 mV
• 250 mA per sensor
Note!
• If the sensor heater is applied, the integrated temperature sensor can not be used. Instead, an external
temperature sensor (Pt100 or FMT131 from Hauser) must be used. The transmitter FMU90 is
available in a version with an input for the external temperature sensor. For details refer to Technical
Information TI00397F.
• The power for the sensor heater can be supplied by the power supply RNB130 from Hauser
Sensor
Operating frequency
FDU90
90 kHz
FDU91
43 kHz
FDU91F
42 kHz
FDU92
30 kHz
FDU93
27 kHz
FDU95 - *1***
(low temperature version)
17 kHz
FDU95 - *2***
(high temperature version)
18 kHz
FDU96
11 kHz