6 Commissioning
Proline Prosonic Flow 90
72
Hauser
6.5
Hardware configuration
6.5.1
Current output: active/passive
The current output can be configured as “active” or “passive” by means of various jumpers on the
I/O board.
#
Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power
supply is switched off before you remove the cover of the electronics compartment.
1.
Switch off power supply.
2.
Remove the I/O board
→
3.
Set the jumpers in accordance with Fig. 47.
"
Caution!
Risk of destroying the measuring device. Make sure that the jumper positions are exactly those
shown in Fig. 47. Incorrectly set jumpers can cause
overcurrents that would destroy either the measuring device or external devices connected
to it.
4.
Installing the I/O board is the reverse of the removal procedure.
A0001044
Fig. 47:
Current output configuration (I/O board)
1
Active current output (default)
2
Passive current output
1
2
Summary of Contents for Prosonic Flow 90
Page 4: ...Brief operating instructions Proline Prosonic Flow 90 4 Endress Hauser...
Page 42: ...4 Wiring Proline Prosonic Flow 90 42 Endress Hauser...
Page 62: ...5 Operation Proline Prosonic Flow 90 62 Endress Hauser...
Page 74: ...7 Maintenance Proline Prosonic Flow 90 74 Endress Hauser...
Page 78: ...8 Accessories Proline Prosonic Flow 90 78 Endress Hauser...
Page 94: ...9 Trouble shooting Proline Prosonic Flow 90 94 Endress Hauser...
Page 108: ...10 Technical data Proline Prosonic Flow 90 108 Endress Hauser...
Page 112: ...Index Proline Prosonic Flow 90 112 Endress Hauser...
Page 114: ...www endress com worldwide BA068D 06 en 11 04 50099981 FM SGLM6 0...