Prosonic
XA202F-B
Safety notes for installation in hazardous areas:
1.) Install according to the manufacturer's instructions and other valid standards and guidelines.
2.) Observe the installation and safety instructions in the operating instructions.
3.) The level detector must not be operated outside of its electrical and thermal performance limits.
4.) The electrical apparatus must be connected to the local plant ground system.
5.) The ultrasonic sensor can be screwed into a durable plastic flange with conductive cladding, a durable unclad plastic flange
with a surface resistance
≤
10
9
Ohm or a metal flange. The uncovered plastic surface may not lie within a pneumatic conveying
stream.The cladding must be connected to the plant grounding system. Conducting or metal flanges are preferred.
6.) The separate version of the sensor can be mounted using the alignment device FAU 40, see figure.
7.) The cable glands may only be replaced by glands of the same type