Proline t-mass 65F, 65I
Hauser
5
Measuring range for the insertion version, US units:
In order to achieve optimum performance it is recommended that under operating conditions the maximum
velocity is limited to a value below 230 ft/sec.
Caution!
The flowrates shown are representative of the calibrated conditions only and do not necessarily reflect what
the meter can measure under operating conditions and actual internal pipe dimensions found on site. To
correctly size and select a meter, it is recommended that you either contact your local Hauser
representative or refer to the Hauser software package Applicator.
Examples in metric units:
Examples in US units:
DN
lb/h
Sm
3
/h at 59°F, 14.7 psi a
scf/min. at 59°F, 14.7 psi a
minimum
maximum
minimum
maximum
minimum
maximum
3"
44
4466
16
1657
9
926
4"
84
8250
30
3060
17
1710
6"
110
16500
40
6120
22.8
3420
8"
176
27500
64
10200
36.5
5700
10"
264
44000
98
16300
55
9120
12"
396
61000
146
22855
82
12768
16"
660
110000
245
40810
136
22800
20"
1100
176000
408
65300
228
36480
24"
1540
253000
570
93870
319
52440
28"
1980
349800
735
129800
410
22504
40"
4400
704000
1630
261200
912
145920
60"
5500
1584000
2040
587750
1140
328320
Line Size
Gas
Process pressure
Temperature
Max. Flowrate
DN
bar a
°C
kg/h
50
Air
1
25
910
50
Air
3
25
3300
50
CO
2
1
25
1300
50
CO
2
3
25
3950
50
Methane
1
25
795
50
Methane
3
25
1500
Line Size
Gas
Process pressure
Temperature
Max. Flowrate
Dia
psia
°F
lb/hr
2"
Air
14.7
77
2002
2"
Air
44.1
77
7260
2"
CO
2
14.7
77
2860
2"
CO
2
44.1
77
8690
2"
Methane
14.7
77
1749
2"
Methane
44.1
77
3300