Proline Promag H 300
10
Hauser
Operable flow range
Over 1000 : 1
Input signal
Input and output versions
External measured values
To increase the accuracy of certain measured variables or to calculate the corrected volume flow, the
automation system can continuously write different measured values to the measuring device:
• Fluid temperature to increase the accuracy of the electrical conductivity (e.g. iTEMP)
• Reference density for calculating the corrected volume flow
Various pressure transmitters and temperature measuring devices can be ordered from Endress
+Hauser: see "Accessories" section → 93
It is recommended to read in external measured values to calculate the following measured variables:
Corrected volume flow
HART protocol
The measured values are written from the automation system to the measuring device via the HART
protocol. The pressure transmitter must support the following protocol-specific functions:
• HART protocol
• Burst mode
Current input
The measured values are written from the automation system to the measuring device via the
Digital communication
The measured values can be written from the automation system to the measuring via:
• FOUNDATION Fieldbus
• PROFIBUS PA
• Modbus RS485
Current input 0/4 to 20 mA
Current input
0/4 to 20 mA (active/passive)
Current span
• 4 to 20 mA (active)
• 0/4 to 20 mA (passive)
Resolution
1 µA
Voltage drop
Typically: 0.6 to 2 V for 3.6 to 22 mA (passive)
Maximum input voltage
≤ 30 V (passive)
Open-circuit voltage
≤ 28.8 V (active)
Possible input variables
• Pressure
• Temperature
• Density
Status input
Maximum input values
• DC –3 to 30 V
• If status input is active (ON): R
i
>3 kΩ
Response time
Adjustable: 5 to 200 ms
Input signal level
• Low signal: DC –3 to +5 V
• High signal: DC 12 to 30 V
Assignable functions
• Off
• Reset the individual totalizers separately
• Reset all totalizers
• Flow override
Summary of Contents for Proline Promag H 300
Page 96: ...www addresses endress com ...