Proline 200 PROFIBUS PA
Electrical connection
Hauser
19
Connection via terminals
10 (0.4)
mm (in)
20 mm
3 mm
1.
2.
3.
4.
5.
6.
A0032239
1. Loosen the securing clamp of the connection compartment cover.
2. Unscrew the connection compartment cover.
3. Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
4. Strip the cable and cable ends. In the case of stranded cables, also fit ferrules.
5. Connect cable in accordance with terminal assignment → 15.
6.
L
WARNING
Housing degree of protection may be voided due to insufficient sealing of the
housing.
‣
Screw in the screw without using any lubricant. The threads on the cover are coated
with a dry lubricant.
Firmly tighten the cable glands.
7. Reverse the removal procedure to reassemble the transmitter.
Summary of Contents for Proline 200 PROFIBUS PA
Page 32: ...www addresses endress com...