Proline 200 PROFIBUS PA
Electrical connection
Hauser
21
5.3
Ensuring the degree of protection
The measuring device fulfills all the requirements for the IP66/67 degree of protection, Type
4X enclosure.
To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following steps
after the electrical connection:
1. Check that the housing seals are clean and fitted correctly.
2. Dry, clean or replace the seals if necessary.
3. Tighten all housing screws and screw covers.
4. Firmly tighten the cable glands.
5. To ensure that moisture does not enter the cable entry:
Route the cable so that it loops down before the cable entry ("water trap").
A0029278
6. Insert dummy plugs into unused cable entries.
5.4
Post-connection check
Are cables or the device undamaged (visual inspection)?
Do the cables used meet the requirements→ 12?
Do the cables have adequate strain relief?
Depending on the device version: are all the device plugs firmly tightened → 18?
Does the supply voltage match the specifications on the transmitter nameplate → 17?
Is the terminal assignment correct ?
Is the terminal assignment or pin assignment of the connector correct?
If supply voltage is present, do values appear on the display module?
Are all housing covers installed and firmly tightened?
Is the securing clamp tightened correctly?
Summary of Contents for Proline 200 PROFIBUS PA
Page 32: ...www addresses endress com...