Proline Promag 53 PROFIBUS DP/PA
Commissioning
Hauser
107
Contents of the downloadfile from the Internet and the CD-ROM:
• All Hauser GSD files (standard and extended format)
• Hauser type files
• Hauser bitmap files
• Useful information relating to the devices
PROFIBUS Profile GSD file:
The function scope of the profile GSD file is defined by the PROFIBUS Profile Specification 3.0. The
function scope is restricted compared to the manufacturer-specific GSD file (complete device
functionality). However, similar devices from different manufacturers can be interchanged with the
profile GSD file without the need to reconfigure (interchangeability).
The following modules are supported with the Profile GSD file:
Name of the PROFIBUS Profile GSD file
Source
Internet (GSD library of the PROFIBUS User Organization)
→
www.PROFIBUS.com
Promag 33 GSD file:
Promag 33 with Profile Version 2.0 is the precursor to the Promag 53.
If Promag 33 is already being operated in the system and the measuring device has to be replaced,
Promag 53 can be used as a replacement device without having to reconfigure the
PROFIBUS DP network.
Further information
“AI Flow” module
→
Analog Input function block 1 / output variable: volume flow
“AI Density”
module
→
Analog Input function block 2 / output variable: mass flow
“Totalizer” module
→
Totalizer function block 1 / output variable: totalized volume flow
ID No.
Profile GSD file
PROFIBUS DP
9741 (Hex)
PA039741.gsd
PROFIBUS PA
9741 (Hex)
PA139741.gsd