Omnigrad M TR13, TC13
4
Measurement range
• RTD: –200 to 600 °C (–328 to 1
112 °F)
• TC: –40 to 1
100 °C (–40 to 2
012 °F)
Performance characteristics
Operating conditions
Ambient temperature
Terminal head
Temperature in °C (°F)
Without mounted head transmitter
Depends on the terminal head used and the cable gland or fieldbus
connector, see 'Terminal heads' section
With mounted head transmitter
–40 to 85 °C (–40 to 185 °F)
With mounted head transmitter and
display
–20 to 70 °C (–4 to 158 °F)
Process pressure
The pressure values to which the actual thermowell can be subjected at the various temperatures and
maximum permitted flow velocity are illustrated by the figure below. Occasionally, the pressure
loading capacity of the process connection can be considerably lower. The maximum allowable
process pressure for a specific thermometer is derived from the lower pressure value of the
thermowell and process connection.
0
50
100
150
200
150
200
250
300
350
400
P (bar)
0
150
200
250
300
350
400
L (mm)
P (bar)
50
100
150
200
A
B
L (in)
6
8
10
12
0
700
2100
2900
P (PSI)
1400
14
16
6
8
10
12
14
16
0
700
2100
2900
P (PSI)
1400
L (mm)
L (in)
P
~ PN100
max.
P
~ PN60
max.
A0013494
3
Maximum permitted process pressure for tube diameter
A
Medium water T = 50 °C (122 °F)
B
Medium superheated steam at T = 400 °C (752 °F)
L
Immersion length
P
Process pressure
___ Thermowell diameter 9 x 1 mm (0.35 in)
- - - Thermowell diameter 12 x 2.5 mm (0.47 in)