Diagnostics and troubleshooting
Tankside Monitor NRF81
94
Hauser
Diagnostic
number
Short text
Remedy instructions
Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
556
Modbus A1-4 analog source
invalid
Set valid analog input selector
C
Warning
557
Modbus B1-4 analog source
invalid
Set valid analog input selector
C
Warning
558
Modbus C1-4 analog source
invalid
Set valid analog input selector
C
Warning
559
Modbus D1-4 analog source
invalid
Set valid analog input selector
C
Warning
560
Calibration mandatory
1. Carry out weight calibration
2. Carry out reference
calibration
3. Carry out drum calibration
C
Alarm
564
DIO B1-2 source no longer
valid
Change input source
C
Warning
565
DIO B3-4 Source not valid
Change input source
C
Warning
566
DIO C1-2 source no longer
valid
Change input source
C
Warning
567
DIO C3-4 source no longer
valid
Change input source
C
Warning
568
DIO D1-2 source no longer
valid
Change input source
C
Warning
569
DIO D3-4 source no longer
valid
Change input source
C
Warning
570
V1 A1-4 analog source
invalid
Set valid analog input selector
C
Warning
571
V1 B1-4 analog source
invalid
Set valid analog input selector
C
Warning
572
V1 C1-4 analog source
invalid
Set valid analog input selector
C
Warning
573
V1 D1-4 analog source
invalid
Set valid analog input selector
C
Warning
574
Modbus A1-4 user value
source invalid
Set valid user value input
selector
C
Warning
575
Modbus B1-4 user value
source invalid
Set valid user value input
selector
C
Warning
576
Modbus C1-4 user value
source invalid
Set valid user value input
selector
C
Warning
577
Modbus D1-4 user value
source invalid
Set valid user value input
selector
C
Warning
578
Modbus A1-4 discrete value
src invalid
Set valid user discrete input
selector
C
Warning
579
Modbus B1-4 disc value
source invalid
Set valid user discrete input
selector
C
Warning
580
Modbus C1-4 disc value
source invalid
Set valid user discrete input
selector
C
Warning
581
Modbus D1-4 discrete value
src invalid
Set valid user discrete input
selector
C
Warning
582
V1 A1-4 user value source
invalid
Set valid user value input
selector
C
Warning
583
V1 B1-4 user value source
invalid
Set valid user value input
selector
C
Warning