![Endress+Hauser Nivotester FTL375P Manual Download Page 41](http://html.mh-extra.com/html/endress-hauser/nivotester-ftl375p/nivotester-ftl375p_manual_2408460041.webp)
Hauser
41
Fault
Reason Remedy
Does not switch
No power
(green LED does not light up)
Check power
Electronic defect
Replace FTL 375 P
Contacts welded together
(after short-circuit)
Replace FTL 375 P;
connect a fuse into contactor
circuit
Measuring transmitter
defective
Replace measuring transmitter
Switches
incorrectly
Incorrect setting of hook switch
for limit signal
Set hook switch to correct
setting on pcb (p. 15…19)
Permanent
alarm signal
Interrupt or short-circuit line to
measuring transmitter
Check line
Measuring transmitter
electronics defective
Replace measuring transmitter
electronics
Fail-safe measuring transmitter
FDL 60/61
connected to FEL 67
Check measuring transmitter
and replace if necessary
Switches
incorrectly after
power failure
FEL 57,
Behaviour during switch-on
test (functional test)
Observe switching behaviour
of FEL 57;
after a power failure block
the system control for up to
about 45 s
Trouble-shooting