Selection of fail-safe mode
The fail-safe mode is controlled by a bridge between terminals 12
and 13 of the Nivotester. The function can be taken from Table 2,
Fig. 7 and Fig. 8
Minimum Fail-safe mode
Maximum Fail-safe mode
1) Relay status on power failure. The green and red LED go out.
Nivotester
Maximum
bridge 12-13
Minimum
no bridge 12-13
FTC 420
Relay de-energises at
maximum
and on
power failure. The red
LED lights
Relay de-energises at
minimum
and on power
failure. The red LED
lights.
FTC 421
Relay de-energises at
maximum
after selected
delay and on power
failure. The red LED
lights
Relay de-energises at
minimum
after selected
delay and on power
failure. The red LED
lights
Table 1
Truth table for fail-safe mode