Electronic Inserts
•
Terminal connections: for max. 2.5 mm
2
•
Measuring frequency: approx. 1.6 MHz
•
Switching delay: approx. 0.5 s
…
approx. 20 s, selectable
•
Minimum/maximum fail-safe switching: selectable with rotary switch
•
Switching indication: red LED
•
Power supply U
∼
: 21 V
…
250 V, 50/60 Hz
•
Connected loads, short-term (max. 40 ms): max. 1.5 A;
max. 375 VA at 250 V;
max. 36 VA at 24 V
•
Maximum voltage drop: 11 V
•
Connected loads, continuous: max. 350 mA;
max. 87 VA at 250 V;
max. 8.4 VA at 24 V
•
Minimum load current at 250 V: 10 mA (2.5 VA)
•
Minimum load current at 24 V: 20 mA (0.5 VA)
•
No-load current (rms): < 5 mA
•
Power supply U =: 10 V
…
55 V
•
Superimposed AC voltage U
pp
: max. 5 V
•
Current consumption: max. 15 mA
•
Load connection: Open Collector; PNP (EC 42) or NPN (EC 43)
•
Switching voltage: max. 55 V
•
Connected load, short-term (max. 1 s): max. 1 A
•
Connected load, continuous: max. 350 mA
•
Residual current with transistor blocked: < 100
µ
A
•
Protected against reverse polarity
•
Power supply U =: 20 V
…
200 V
or
Power supply U
∼
: 21 V
…
250 V, 50/60 Hz
•
Current consumption (rms): max. 5 mA
•
Peak inrush current: max. 200 mA, max. 5 ms
•
Pulse current: max. 50 mA, max. 5 ms
•
Pulse frequency: approx. 1.5 s
•
Output: potential-free change-over contact
•
Contact load capacity:
U
∼
max. 250 V, I
∼
max. 6 A,
P
∼
max. 1500 VA (cos
ϕ
= 1) or P
∼
max. 750 VA, (cos
ϕ ≥
0.7)
U = max. 250 V, I = max. 6 A, P = max.200 W
•
Operating life: min. 10
5
switchings at max. contact load
•
Additional switching delay: max. 1.5 s
Type Key
See Page 11 for order specification key and order code.
EMC
Electromagnetic compatibility:
•
Interference Emission to EN 61326, Electrical Equipment Class A
•
Interference Immunity to EN 61326
•
EMC Test Procedures see TI 241F/00/en
Subject to modification
Electronic Insert EC 40
for AC
(Two-Wire Connection)
Electronic Inserts EC 42, EC 43
for DC
(Three-wire Connection)
Electronic Insert EC 44
for DC and AC
(Relay Output)
Nivocompact FTC 831
Technical Data
6
Summary of Contents for nivocompact FTC 831
Page 2: ......
Page 4: ...Nivocompact FTC 831 2...
Page 7: ...Fig 2 Dimensions Nivocompact FTC 831 Technical Data 5...
Page 31: ......