Operation
Micropilot S FMR540 4 to 20 mA HART
40
Hauser
5.5
HART communication
Apart from local operation, you can also parameterise the measuring device and view measured
values by means of a HART protocol. There are two options available for operation:
• Operation via the universal handheld operating unit, Field Communicator 375, 475.
• Operation via the Personal Computer (PC) using the operating program
(e.g. FieldCare; Connections,
56).
!
Note!
The Micropilot S can also be operated locally using the keys. If operation is prevented by the keys
being locked locally, parameter entry via communication is not possible either.
5.5.1
Protocol specific data
5.5.2
Operation with Field Communicator 375, 475
All device functions can be adjusted via menu operation with the Field Communicator 375, 475.
!
Note!
Further information on the HART handheld unit is given in the respective operating manual
included in the transport bag of the Field Communicator 375, 475.
Manufacturer-ID
000011 hex
Device Type Code
001F hex
Transmitter specific revision
01 hex
HART specification
5.0
DD-Files
Information and files can be found on:
• www.endress.com
• www.hartcomm.org
Load HART
Min. 250
Ω
Device variables
Primary value: level or volume
1)
1)
according to configuration
Features supported
• Burst mode
• Additional Transmitter Status