Commissioning

Micropilot FMR63B HART

30

Hauser

13.4   Configuring the device address via software

See "HART address" parameter

Enter the address to exchange data via the HART protocol.

• Guidance → Commissioning → HART address

• Application → HART output → Configuration → HART address

13.5   Setting the operating language

13.5.1   Local display

Setting the operating language

To set the operating language, the display first needs to be unlocked:

1. Press the  key for at least 2 s.

 A dialog box appears.

2. Unlock the display operation.
3. Select the 

Language

 parameter in the main menu.

4. Press the  key.
5. Select the desired language with the  or  key.
6. Press the  key.

Display operation locks automatically (except in the 

Safety mode

 wizard):

• after 1 min on the main page if no key has been pressed

• after 10 min within the operating menu if no key has been pressed

13.5.2   Operating tool

Set display language
System → Display → Language
Selection in the 

Language

 parameter; Visibility depends on order options or device settings

Summary of Contents for Micropilot FMR63B

Page 1: ...are not a substitute for the Operating Instructions pertaining to the device Detailed information is provided in the Operating Instructions and other documentation Available for all device versions vi...

Page 2: ...Micropilot FMR63B HART 2 Endress Hauser Order code Ext ord cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555...

Page 3: ...1 10 4 Post mounting check 14 11 Electrical connection 15 11 1 Connecting requirements 15 11 2 Connecting the device 16 11 3 Ensuring the degree of protection 23 11 4 Post connection check 23 12 Opera...

Page 4: ...ry NOTICE This symbol contains information on procedures and other facts which do not result in personal injury 1 2 Symbols for certain types of information and graphics Permitted Procedures processes...

Page 5: ...observed the measuring device may be used for the following measurements only Measured process variables level distance signal strength Calculable process variables volume or mass in any shape of vess...

Page 6: ...l related area e g explosion protection pressure equipment safety Check the nameplate to verify if the device ordered can be put to its intended use in the approval related area Observe the specificat...

Page 7: ...evice features on the delivery note Device Viewer www endress com deviceviewer manually enter the serial number from the nameplate All the information about the measuring device is displayed Endress H...

Page 8: ...kaging or by the process connection Always secure lifting equipment slings eyes etc at the process connection and never lift the device by the electronic housing or sensor Pay attention to the center...

Page 9: ...Hauser 9 10 2 Mounting requirements 10 2 1 Internal vessel fittings A0031777 Avoid internal fittings point level switches temperature sensors struts vacuum rings heating coils baffles etc inside the...

Page 10: ...it is perpendicular to the product surface The maximum reach of the antenna can be reduced or additional interference signals can occur if the antenna is not installed perpendicular to the product 10...

Page 11: ...00 mm 12 in 80 to 100 mm 3 2 to 4 in 450 mm 18 in 100 to 150 mm 4 to 6 in 550 mm 22 in 150 mm 6 in 850 mm 34 in In the case of longer nozzles reduced measuring performance must be expected Please note...

Page 12: ...d in the table 10 3 3 Antenna PTFE cladded flush mount 80 mm 3 in The cladding on the antenna also acts as a process seal An additional seal is not required for installation Information about the moun...

Page 13: ...t housing C Dual compartment housing D Dual compartment housing L form 1 Locking screw NOTICE The housing cannot be unscrewed fully Loosen the external locking screw by a maximum of 1 5 turns If the s...

Page 14: ...ectronics compartment cover back onto the transmitter housing If fitted tighten the screw of the cover lock using the Allen key 0 7 Nm 0 52 lbf ft 0 2 Nm 0 15 lbf ft 10 3 6 Closing the housing covers...

Page 15: ...ICE If the securing screw is not positioned correctly the cover cannot provide secure sealing Open the cover slacken the screw of the cover lock with a maximum of 2 turns so that the screw does not fa...

Page 16: ...pplications in hazardous areas for the safety instructions For optimum electromagnetic compatibility Keep the potential matching line as short as possible Observe a cross section of at least 2 5 mm2 1...

Page 17: ...vant protocol specifications A suitable circuit breaker must be provided for the device in accordance with IEC EN61010 1 11 2 2 Cable specification Rated cross section Supply voltage 0 5 to 2 5 mm2 20...

Page 18: ...as a Mounted accessory via the product structure Devices without optional overvoltage protection Equipment from Endress Hauser fulfills the requirements of the product standard IEC DIN EN 61326 1 Tabl...

Page 19: ...breaker should be provided for the device in accordance with IEC EN 61010 The cables must be adequately insulated with due consideration given to the supply voltage and the overvoltage category The co...

Page 20: ...63B HART 20 Endress Hauser 11 2 6 Terminal assignment Single compartment housing 1 2 3 A0042594 3 Connection terminals and ground terminal in the connection compartment 1 Positive terminal 2 Negative...

Page 21: ...T Electrical connection Endress Hauser 21 Dual compartment housing 1 2 3 A0042803 4 Connection terminals and ground terminal in the connection compartment 1 Positive terminal 2 Negative terminal 3 Int...

Page 22: ...and ground terminal in the connection compartment 1 Positive terminal 2 Negative terminal 3 Internal ground terminal 11 2 7 Cable entries 1 1 1 1 2 A B C D 2 2 2 A0046584 A Single compartment housing...

Page 23: ...uded with the delivery along with the corresponding documentation Thread NPT1 2 IP66 68 TYPE 4X 6P Dummy plug transport protection IP22 TYPE 2 HAN7D plug 90 degrees IP65 NEMA Type 4X M12 plug When hou...

Page 24: ...tches on the HART electronic insert Display on off 1 2 on off 3 4 A0046129 6 Operating keys and DIP switches on the HART electronic insert 1 Operating key for reset password for Bluetooth login and Ma...

Page 25: ...s access code protects the device configuration from unauthorized access If an incorrect access code is entered the user obtains the access rights of the Operator role 12 4 Access to the operating men...

Page 26: ...sly takes the user back up a level in the menu Press and hold the keys simultaneously to return to the upper level 12 4 2 Operation via Bluetooth wireless technology optional Requirement Device with d...

Page 27: ...password changed by the user is also saved in the Bluetooth display 12 5 Access to the operating menu via the operating tool Access via the operating tool is possible Via HART communication e g Commu...

Page 28: ...guration parameters Guidance menu Commissioning wizard 13 1 Preliminaries The measuring range and the unit in which the measured value is transmitted correspond to the data on the nameplate LWARNING T...

Page 29: ...Connection for Commubox FXA195 and AMS TrexTM device communicator 4 AMS TrexTM device communicator 5 Computer with operating tool e g DeviceCare FieldCare AMS Device View SIMATIC PDM 6 Commubox FXA19...

Page 30: ...display first needs to be unlocked 1 Press the key for at least 2 s A dialog box appears 2 Unlock the display operation 3 Select the Language parameter in the main menu 4 Press the key 5 Select the de...

Page 31: ...ssioning with the Commissioning wizard In FieldCare DeviceCare SmartBlue and on the display the Commissioning wizard is available to guide the user through the initial commissioning steps Complete thi...

Page 32: ...www addresses endress com 71575926 71575926...

Reviews: