Brief Operating Instructions

Micropilot FMR62B

Free space radar

HART

These Brief Operating Instructions are not a substitute for the

Operating Instructions pertaining to the device.
Detailed information is provided in the Operating Instructions

and other documentation.
Available for all device versions via:

• Internet: www.endress.com/deviceviewer

• Smartphone/tablet: Hauser Operations app

KA01588F/00/EN/01.22-00

71575925

2022-08-01

Summary of Contents for Micropilot FMR62B

Page 1: ...are not a substitute for the Operating Instructions pertaining to the device Detailed information is provided in the Operating Instructions and other documentation Available for all device versions vi...

Page 2: ...Micropilot FMR62B HART 2 Endress Hauser Order code Ext ord cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555...

Page 3: ...1 10 4 Post mounting check 17 11 Electrical connection 17 11 1 Connecting requirements 17 11 2 Connecting the device 19 11 3 Ensuring the degree of protection 25 11 4 Post connection check 25 12 Opera...

Page 4: ...ry NOTICE This symbol contains information on procedures and other facts which do not result in personal injury 1 2 Symbols for certain types of information and graphics Permitted Procedures processes...

Page 5: ...observed the measuring device may be used for the following measurements only Measured process variables level distance signal strength Calculable process variables volume or mass in any shape of vess...

Page 6: ...l related area e g explosion protection pressure equipment safety Check the nameplate to verify if the device ordered can be put to its intended use in the approval related area Observe the specificat...

Page 7: ...evice features on the delivery note Device Viewer www endress com deviceviewer manually enter the serial number from the nameplate All the information about the measuring device is displayed Endress H...

Page 8: ...kaging or by the process connection Always secure lifting equipment slings eyes etc at the process connection and never lift the device by the electronic housing or sensor Pay attention to the center...

Page 9: ...Hauser 9 10 2 Mounting requirements 10 2 1 Internal vessel fittings A0031777 Avoid internal fittings point level switches temperature sensors struts vacuum rings heating coils baffles etc inside the...

Page 10: ...it is perpendicular to the product surface The maximum reach of the antenna can be reduced or additional interference signals can occur if the antenna is not installed perpendicular to the product 10...

Page 11: ...es reduced measuring performance must be expected Please note the following The end of the nozzle must be smooth and free from burrs The edge of the nozzle should be rounded Mapping must be performed...

Page 12: ...in the table 10 3 3 Antenna PTFE cladded flush mount 50 mm 2 in The cladding on the antenna also acts as a process seal An additional seal is not required for installation Mounting cladded flanges No...

Page 13: ...g must be performed Please contact the manufacturer s support department for applications with nozzles that are higher than indicated in the table 10 3 4 Antenna PTFE cladded flush mount 80 mm 3 in Th...

Page 14: ...o 105 Nm ASME NPS 3 Cl 150 4 65 to 95 Nm NPS 3 Cl 300 8 40 to 55 Nm NPS 4 Cl 150 8 45 to 65 Nm NPS 4 Cl 300 8 55 to 80 Nm NPS 6 Cl 150 8 85 to 125 Nm NPS 6 Cl 300 12 60 to 85 Nm NPS 8 Cl 150 8 115 to...

Page 15: ...nozzle should be rounded Mapping must be performed Please contact the manufacturer s support department for applications with nozzles that are higher than indicated in the table 10 3 5 Turning the ho...

Page 16: ...h off the supply voltage before opening the measuring device 2 1 4 0 7 Nm 3 4 A0038224 1 If fitted release the screw of the cover lock for the electronics compartment cover using the Allen key 2 Unscr...

Page 17: ...securing screws and cover lock tightened securely Does the measuring device comply with the measuring point specifications For example Process temperature Process pressure Ambient temperature Measurin...

Page 18: ...evice is connected 1 1 1 B C D 1 A A0046583 A Single compartment housing plastic B Single compartment housing aluminum C Dual compartment housing D Dual compartment housing L form 1 Ground terminal fo...

Page 19: ...11 2 1 Supply voltage The supply voltage depends on the selected type of device approval Non hazardous Ex d Ex e 10 5 to 35 VDC Ex i 10 5 to 30 VDC Nominal current 4 to 20 mA The power unit must be te...

Page 20: ...e is always necessary in the case of a low impedance power supply Take the voltage drop into consideration Maximum 6 V for a 250 communication resistor 11 2 4 Overvoltage protection The overvoltage pr...

Page 21: ...be connected to the outer ground terminal of the device before the power supply lines are connected A suitable circuit breaker should be provided for the device in accordance with IEC EN 61010 The ca...

Page 22: ...62B HART 22 Endress Hauser 11 2 6 Terminal assignment Single compartment housing 1 2 3 A0042594 3 Connection terminals and ground terminal in the connection compartment 1 Positive terminal 2 Negative...

Page 23: ...T Electrical connection Endress Hauser 23 Dual compartment housing 1 2 3 A0042803 4 Connection terminals and ground terminal in the connection compartment 1 Positive terminal 2 Negative terminal 3 Int...

Page 24: ...and ground terminal in the connection compartment 1 Positive terminal 2 Negative terminal 3 Internal ground terminal 11 2 7 Cable entries 1 1 1 1 2 A B C D 2 2 2 A0046584 A Single compartment housing...

Page 25: ...uded with the delivery along with the corresponding documentation Thread NPT1 2 IP66 68 TYPE 4X 6P Dummy plug transport protection IP22 TYPE 2 HAN7D plug 90 degrees IP65 NEMA Type 4X M12 plug When hou...

Page 26: ...tches on the HART electronic insert Display on off 1 2 on off 3 4 A0046129 6 Operating keys and DIP switches on the HART electronic insert 1 Operating key for reset password for Bluetooth login and Ma...

Page 27: ...s access code protects the device configuration from unauthorized access If an incorrect access code is entered the user obtains the access rights of the Operator role 12 4 Access to the operating men...

Page 28: ...sly takes the user back up a level in the menu Press and hold the keys simultaneously to return to the upper level 12 4 2 Operation via Bluetooth wireless technology optional Requirement Device with d...

Page 29: ...password changed by the user is also saved in the Bluetooth display 12 5 Access to the operating menu via the operating tool Access via the operating tool is possible Via HART communication e g Commu...

Page 30: ...guration parameters Guidance menu Commissioning wizard 13 1 Preliminaries The measuring range and the unit in which the measured value is transmitted correspond to the data on the nameplate LWARNING T...

Page 31: ...Connection for Commubox FXA195 and AMS TrexTM device communicator 4 AMS TrexTM device communicator 5 Computer with operating tool e g DeviceCare FieldCare AMS Device View SIMATIC PDM 6 Commubox FXA19...

Page 32: ...display first needs to be unlocked 1 Press the key for at least 2 s A dialog box appears 2 Unlock the display operation 3 Select the Language parameter in the main menu 4 Press the key 5 Select the de...

Page 33: ...ssioning with the Commissioning wizard In FieldCare DeviceCare SmartBlue and on the display the Commissioning wizard is available to guide the user through the initial commissioning steps Complete thi...

Page 34: ......

Page 35: ......

Page 36: ...www addresses endress com 71575925 71575925...