Electrical connection
Micropilot FMR62B HART
20
Hauser
Cable outer diameter
The cable outer diameter depends on the cable gland used
• Coupling, plastic:
⌀5 to 10 mm (0.2 to 0.38 in)
• Coupling, nickel-plated brass:
⌀7 to 10.5 mm (0.28 to 0.41 in)
• Coupling, stainless steel:
⌀7 to 12 mm (0.28 to 0.47 in)
11.2.3 4 to 20 mA HART
2
3
4
Y
+
+
-
-
I
1
mA
A0028908
2
Block diagram of HART connection
1
Device with HART communication
2
HART communication resistor
3
Power supply
4
Multimeter or ammeter
The HART communication resistor of 250 Ω in the signal line is always necessary in the
case of a low-impedance power supply.
Take the voltage drop into consideration:
Maximum 6 V for a 250 Ω communication resistor
11.2.4 Overvoltage protection
The overvoltage protection can optionally be ordered as a "Mounted accessory" via the product
structure
Devices without optional overvoltage protection
Equipment from Hauser fulfills the requirements of the product standard IEC / DIN
EN 61326-1 (Table 2 Industrial Environment).
Depending on the type of port (DC power supply, input/output port) different testing levels
according to IEC / DIN EN 61326-1 against transient overvoltages (Surge) are applied (IEC /
DIN EN 61000-4-5 Surge):
Test level on DC power ports and input/output ports is 1
000 V line to earth